1224.39.6.5.5 Examination or Treatment Room(s)
Go To Full Code Chapter
Examination or treatment rooms are optional. If provided, examination and/or treatment rooms must be readily accessible, but may be shared with other units or compatible departments. Provisions shall be made to preserve patient privacy from observation from outside the exam room through an open door. The room shall have a minimum area of 80 square feet (7.4 m2), the least dimension of which 8 feet (2438 mm).