2.5-4.4.2.2 Essential Electrical System Connections
Guidelines for Design and Construction of Residential Health, Care, and Support Facilities 2018 of Michigan > 2.5 Building Systems > 2.5-4 Electrical Systems > 2.5-4.4 Electrical Requirements for Ventilator-Dependent Resident Rooms and Areas > 2.5-4.4.2 > 2.5-4.4.2.2 Essential Electrical System Connections
Go To Full Code Chapter
- Heating equipment provided for ventilator-dependent resident rooms shall be connected to the essential electrical system.
- Task lighting connected to the essential electrical system shall be provided for each ventilator-dependent resident room.
Related Code Sections
2.5-4.4.2.2 Building Systems, Essential Electrical System Connections
Heating equipment provided for ventilator-dependent resident rooms shall be connected to the essential electrical system. Task lighting connected ...
Guidelines for Design and Construction of Residential Health, Care, and Support Facilities 2018 of Michigan > 2.5 Building Systems > 2.5-4 Electrical Systems > 2.5-4.4 Electrical Requirements for Ventilator-Dependent Resident Rooms and Areas > 2.5-4.4.2 > 2.5-4.4.2.2 Essential Electrical System Connections
2.1-8.3.5.1 Common Elements for Outpatient Facilities, Hand-Washing Station Sinks and Scrub Sinks
for operation shall be connected to the essential electrical system ...
*2.1-8.3.5.1 Common Elements for Hospitals, Hand-Washing Station Sinks and Scrub Sinks
Any required hand-washing station or scrub sink that depends on the building electrical service for operation shall be connected to the essential ...
(A) Special Occupancies,
Those functions of patient care depending on lighting or appliances that are connected to the essential electrical system shall be divided ...
517.32 Special Occupancies, Branches Requiring Automatic Connection
Those functions of patient care depending on lighting or appliances that are connected to the essential electrical system shall be divided ...