// CODE SNIPPET
712.1.3 Escalator Openings
JUMP TO FULL CODE CHAPTER
Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, vertical openings for escalators shall be permitted where protected in accordance with Section 712.1.3.1 or 712.1.3.2.
Protection by a draft curtain and closely spaced sprinklers in accordance with NFPA 13 shall be permitted where the area of the vertical opening between stories does not exceed twice the horizontal projected area of the escalator. In other than Groups B and M, this application is limited to openings that do not connect more than four stories.
Protection of the vertical opening by approved shutters at every penetrated floor shall be permitted in accordance with this section. The shutters shall be of noncombustible construction and have a fire-resistance rating of not less than 1.5 hours. The shutter shall be so constructed as to close immediately upon the actuation of a smoke detector installed in accordance with Section 907.3.1 and shall completely shut off the well opening. Escalators shall cease operation when the shutter begins to close. The shutter shall operate at a speed of not more than 30 feet per minute (152.4 mm/s) and shall be equipped with a sensitive leading edge to arrest its progress where in contact with any obstacle, and to continue its progress on release there from.
Related Code Sections
712.1.3 Fire and Smoke Protection Features, Escalator Openings
Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, vertical openings for escalators ...
2020 Building Code of New York State > 7 Fire and Smoke Protection Features > 712 Vertical Openings > 712.1 General > 712.1.3 Escalator Openings
712.1.3 Fire and Smoke Protection Features, Escalator Openings
Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, vertical openings for escalators ...
Building Code 2015 of New York State > 7 Fire and Smoke Protection Features > 712 Vertical Openings > 712.1 General > 712.1.3 Escalator Openings
1103.4.5 Construction Requirements for Existing Buildings, Escalators in Group B and M Occupancies
In Group B and M occupancies, escalators creating vertical openings connecting any number of stories shall be protected by either 1-hour fire ...
Fire Code 2015 of New York State > 11 Construction Requirements for Existing Buildings > 1103 Fire Safety Requirements for Existing Buildings > 1103.4 Vertical Openings > 1103.4.5 Escalators in Group B and M Occupancies
1103.4.5 Construction Requirements for Existing Buildings, Escalators in Group B and M Occupancies
In Group B and M occupancies, escalators creating vertical openings connecting any number of stories shall be protected by either 1-hour fire ...
2020 Fire Code of NYS > 11 Construction Requirements for Existing Buildings > 1103 Fire Safety Requirementsfor Existing Buildings > 1103.4 Vertical Openings > 1103.4.5 Escalators in Group B and M Occupancies
1103.4.6 Construction Requirements for Existing Buildings, Escalators Connecting Four or Fewer Stories
In other than Group B and M occupancies, escalators creating vertical openings connecting four or fewer stories shall be protected by either 1-hour ...
2020 Fire Code of NYS > 11 Construction Requirements for Existing Buildings > 1103 Fire Safety Requirementsfor Existing Buildings > 1103.4 Vertical Openings > 1103.4.6 Escalators Connecting Four or Fewer Stories