N1106.5 (R406.5) ERI-Based Compliance
Go To Full Code Chapter
Compliance based on an ERI analysis requires that the rated proposed design and confirmed built dwelling be shown to have an ERI less than or equal to the appropriate value indicated in Table N1106.5 when compared to the ERI reference design.
TABLE N1106.5
(R406.5)
MAXIMUM ENERGY RATING INDEX
CLIMATE ZONE | ENERGY RATING INDEX |
0—1 | 52 |
2 | 52 |
3 | 51 |
4 | 54 |
5 | 55 |
6 | 54 |
7 | 53 |
8 | 53 |