409.5 Equipment Shutoff Valve
JUMP TO FULL CODE CHAPTER
Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room as the appliance, not further than 6 feet (1829 mm) from the appliance, and shall be installed upstream from the union, connector or quick disconnect device it serves. Such shutoff valves shall be provided with access.
Exception: Shutoff valves for vented decorative appliances and decorative appliances for installation in vented fireplaces shall not be prohibited from being installed in an area remote from the appliance where such valves are provided with ready access. Such valves shall be permanently identified and shall serve no other equipment. Piping from the shutoff valve to within 3 feet (914 mm) of the appliance connection shall be sized in accordance with Section 402.
Exception: Shutoff valves for vented decorative appliances and decorative appliances for installation in vented fireplaces shall not be prohibited from being installed in an area remote from the appliance where such valves are provided with ready access. Such valves shall be permanently identified and shall serve no other equipment. Piping from the shutoff valve to within 3 feet (914 mm) of the appliance connection shall be sized in accordance with Section 402.
Equipment shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer's instructions.
Shutoff valves for vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces shall be permitted to be installed in an area remote from the appliances where such valves are provided with ready access. Such valves shall be permanently identified and shall serve no other appliance. The piping from the manifold to within 6 feet (1829 mm) of the appliance shall be designed and installed in accordance with Sections 401 through 408.
Where the appliance shutoff valve is installed at a manifold, such shutoff valve shall be located within 50 ft (15 240 mm) of the appliance served and shall be readily accessible and permanently identified. The piping from the manifold to within 6 feet (1829 mm) of the appliance shall be designed and installed in accordance with Sections 401 through 408.
Exception: This section is not applicable to appliances installed outdoors.
Exception: This section is not applicable to appliances installed outdoors.
Related Code Sections
409.5 Gas Piping Installations, Equipment Shutoff Valve
with ready access. Such valves shall be permanently identified and shall serve no other equipment. Piping from the shutoff valve to within 3 feet (914 mm ...
2010 Fuel Gas Code of NY > 4 Gas Piping Installations > 409 Shutoff Valves > 409.5 Equipment Shutoff Valve
G2420.5 Fuel Gas, (409.5) Equipment Shutoff Valve
with ready access. Such valves shall be permanently identified and shall serve no other equipment. Piping from the shutoff valve to within 3 feet (914mm ...
2010 Residential Code of NY > 24 Fuel Gas > G2420 (409) Gas Shutoff Valves > G2420.5 (409.5) Equipment Shutoff Valve
406.3.4 Gas Piping Installations, Valve Isolation
, such appliances or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s) ...
2020 Fuel Gas Code of NYS > 4 Gas Piping Installations > 406 Inspection, Testing and Purging > 406.3 Test Preparation > 406.3.4 Valve Isolation
406.3.4 Gas Piping Installations, Valve Isolation
, such appliances or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s) ...
2010 Fuel Gas Code of NY > 4 Gas Piping Installations > 406 Inspection, Testing and Purging > 406.3 Test Preparation > 406.3.4 Valve Isolation
406.3.4 Gas Piping Installations, Valve Isolation
, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s) ...
Fuel Gas Code 2015 of New York State > 4 Gas Piping Installations > 406 (IFGS) Inspection, Testing and Purging > 406.3 Test Preparation > 406.3.4 Valve Isolation