E3908.2 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed)
JUMP TO FULL CODE CHAPTER
Exposed, normally noncurrent-carrying metal parts of fixed equipment supplied by or enclosing conductors or components that are likely to become energized shall be connected to the equipment grounding conductor where any of the following conditions apply:
- Where within 8 feet (2438 mm) vertically or 5 feet (1524 mm) horizontally of earth or grounded metal objects and subject to contact by persons;
- Where located in a wet or damp location and not isolated; or
- Where in electrical contact with metal.
Related Code Sections
E3908.2 Power and Lighting Distribution, Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed)
Exposed, normally noncurrent-carrying metal parts of fixed equipment supplied by or enclosing conductors or components that are likely to become ...
2017 FBC - Residential, 6th edition > 39 Power and Lighting Distribution > E3908 Grounding > E3908.2 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed)
E3908.2 Power and Lighting Distribution, Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed)
Exposed, normally noncurrent-carrying metal parts of fixed equipment supplied by or enclosing conductors or components that are likely to become ...
2014 FBC - Residential, 5th edition > 39 Power and Lighting Distribution > E3908 Grounding > E3908.2 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed)
E4206.10.2 Swimming Pools [Electrical Provisions], Wiring Methods
bonding jumper in the forming shell shall be covered with, or encapsulated in, a suitable potting compound to protect such connection from the possible ...
2014 FBC - Residential, 5th edition > 42 Swimming Pools [Electrical Provisions] > E4206 Equipment Installation > E4206.10 Underwater Audio Equipment > E4206.10.2 Wiring Methods
E4206.10.2 Swimming Pools [Electrical Provisions], Wiring Methods
bonding jumper in the forming shell shall be covered with, or encapsulated in, a suitable potting compound to protect such connection from the possible ...
2017 FBC - Residential, 6th edition > 42 Swimming Pools [Electrical Provisions] > E4206 Equipment Installation > E4206.10 Underwater Audio Equipment > E4206.10.2 Wiring Methods
E3904.3 Power and Lighting Distribution, Securing and Supporting
Raceways, cable assemblies, boxes, cabinets and fittings shall be securely fastened in place ...
2014 FBC - Residential, 5th edition > 39 Power and Lighting Distribution > E3904 General Installation Requirements > E3904.3 Securing and Supporting