306.5 Equipment and Appliances on Roofs or Elevated Structures
JUMP TO FULL CODE CHAPTER
Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet (4877 mm) above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall.
Permanent ladders installed to provide the required access shall comply with the following minimum design criteria:
Permanent ladders installed to provide the required access shall comply with the following minimum design criteria:
- The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm).
- Ladders shall have rung spacing not to exceed 14 inches (356 mm) on center. The uppermost rung shall be not greater than 24 inches (610 mm) below the upper edge of the roof hatch, roof or parapet, as applicable.
- Ladders shall have a toe spacing not less than 6 inches (152 mm) deep.
- There shall be not less than 18 inches (457 mm) between rails.
- Rungs shall have a diameter not less than 0.75-inch (19 mm) and be capable of withstanding a 300-pound (136.1 kg) load.
- Ladders over 30 feet (9144 mm) in height shall be provided with offset sections and landings capable of withstanding 100 pounds per square foot (488.2 kg/ m2). Landing dimensions shall be not less than 18 inches (457 mm) and not less than the width of the ladder served. A guard rail shall be provided on all open sides of the landing.
- Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climbing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintained from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed.
- Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches (762 mm) by 30 inches (762 mm) centered in front of the ladder.
- Ladders shall be protected against corrosion by approved means.
- Access to ladders shall be provided at all times.
Exception: This section shall not apply to Group R-3 occupancies.
Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25-percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service, repair or maintenance. The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm) above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the International Building Code. Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33-percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with ladders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the International Building Code in the path of travel to and from appliances, fans or equipment requiring service.
Related Code Sections
306.5 General Regulations, Equipment and Appliances on Roofs or Elevated Structures
Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb ...
Fuel Gas Code 2015 of Utah > 3 General Regulations > 306 (IFGC) Access and Service Space > 306.5 Equipment and Appliances on Roofs or Elevated Structures
306.5 General Regulations, Equipment and Appliances on Roofs or Elevated Structures
Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb ...
Fuel Gas Code 2018 of Utah > 3 General Regulations > 306 (IFGC) Access and Service Space > 306.5 Equipment and Appliances on Roofs or Elevated Structures
306.5 General Regulations, Equipment and Appliances on Roofs or Elevated Structures
Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have ...
Mechanical Code 2018 of Utah > 3 General Regulations > 306 Access and Service Space > 306.5 Equipment and Appliances on Roofs or Elevated Structures
306.5 General Regulations, Equipment and Appliances on Roofs or Elevated Structures
Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have ...
Mechanical Code 2015 of Utah > 3 General Regulations > 306 Access and Service Space > 306.5 Equipment and Appliances on Roofs or Elevated Structures
306.5.1 General Regulations, Sloped Roofs
Where appliances, equipment , fans or other components that require service are installed on a roof having a slope of 3 units vertical in 12 units ...
Fuel Gas Code 2018 of Utah > 3 General Regulations > 306 (IFGC) Access and Service Space > 306.5 Equipment and Appliances on Roofs or Elevated Structures > 306.5.1 Sloped Roofs