§42-01 Entrance Doors, Locks and Intercommunication Systems
JUMP TO FULL CODE CHAPTER
(a) Bulkhead doors and scuttles shall have no key locks and shall not be locked by a key at any time. The only permissible and acceptable means of securing a bulkhead door or scuttle is by means of a movable bolt or hook on the inside.
(b) Section 15.10(n) of the current departmental rules and regulations in its last un-numbered paragraph provides as follows: "All passageways required under these rules shall be not less than seven feet (7'0") in height and not less than three feet (3'0") in width and shall at all times be kept dear and unobstructed. Doors and gates at the end of such passageways are prohibited, except that a door or gate equipped with an approved-type knob or panic bolt which shall be readily openable from the inside will be permitted at the building line. Doors and gates provided with key locks or padlocks are prohibited."
(c) Where an entrance door leading from a vestibule to the main entrance hall or lobby is equipped with one or more automatic self-closing and self-locking doors, the entrance door from the street to the vestibule need not be equipped with automatic self-closing and self-locking doors.
(d) Every entrance from the street, court, yard or cellar to a class A multiple dwelling erected or converted after January 1, 1968 containing eight or more apartments shall be equipped with automatic self-closing and self-locking doors. Such multiple dwelling, as aforesaid, shall also be equipped with an intercommunication system to be located at the required main entrance door.
(e) On or after January 1, 1969, every entrance from the street, court, yard or cellar to a class A multiple dwelling erected or converted prior to January 1, 1968 containing eight or more apartments, shall be equipped with automatic self-closing and self-locking doors and shall also be equipped with an intercommunication system.
(f) Every self-locking door required under this section shall be installed and maintained so as to be readily openable from the inside without the use of keys.
(g) The minimal devices acceptable for the intercommunication system shall be a bell or buzzer system, or a speaking and listening device to permit communication by voice between the occupant of each apartment and a person outside such required main entrance door, and a return buzzer mechanism to release or open the lock to the aforesaid required door.
(h) The bell and intercommunication system shall be located at the required main entrance door so that a person may readily reach the door when the unlocking buzzer is activated.
(i) No push button device shall be more than six feet from the floor and the speaking and listening device shall be installed to be not less than four feet and not more than five feet from the floor.
(j) The device or devices for the intercommunication system installed in the apartment shall be readily accessible to the occupant.
(k) The device or devices for the intercommunication system installed hereunder under shall be of a type and kind approved by the Department of Buildings or previously approved by the Board of Standards and Appeals.
(l) Devices which have been previously installed and which are in good condition and performing in an adequate manner may, in the discretion of the department, be accepted.
Related Code Sections
Appendix A Selected Rules of the Department of Buildings [PDF] (page 5)
Appliances in Multiple Dwellings Ch. 42 Entrance Doors, Locks and Intercommunication Systems §42-01 Entrance Doors, Locks and Intercommunication Systems Ch ...
Appendix A Selected Rules of the Department of Buildings [PDF] (page 121)
the Department of Buildings before any vertical flue or chimney is constructed. CHAPTER 42 ENTRANCE DOORS, LOCKS AND INTERCOMMUNICATION SYSTEMS §42-01 ...
1008.4.4 Means of Egress, Intercommunication System
Buildings containing eight or more dwelling units shall be provided with an intercommunication system located at the door giving access to the main ...
NYC Building Code 2008 > 10 Means of Egress > 1008 Doors, Gates and Turnstiles > 1008.4 Security Requirements for Doors and Windows > 1008.4.4 Intercommunication System
1008.4.4 Means of Egress, Intercommunication System
Buildings containing eight or more dwelling units shall be provided with an intercommunication system located at the door giving access to the main ...
NYC Building Code 2014 > 10 Means of Egress > 1008 Doors, Gates and Turnstiles > 1008.4 Security Requirements for Doors and Windows > 1008.4.4 Intercommunication System
1010.4.4 Means of Egress, Intercommunication System
Buildings containing eight or more dwelling units shall be provided with an intercommunication system located at the door giving access to the main ...
NYC Building Code 2022 > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.4 Security Requirements for Doors and Windows > 1010.4.4 Intercommunication System