1910.303(h)(4) Entrance and Access to Work Space
Go To Full Code Chapter
1910.303(h)(4)(i)
At least one entrance not less than 610 mm (24 in.) wide and 1.98 m (6.5 ft) high shall be provided to give access to the working space about electric equipment.
1910.303(h)(4)(i)(A)
On switchboard and control panels exceeding 1.83 m (6.0 ft) in width, there shall be one entrance at each end of such boards unless the location of the switchboards and control panels permits a continuous and unobstructed way of exit travel, or unless the work space required in paragraph (h)(5)(i) of this section is doubled.
1910.303(h)(4)(i)(B)
Where one entrance to the working space is permitted under the conditions described in paragraph (h)(4)(i)(A) of this section, the entrance shall be located so that the edge of the entrance nearest the switchboards and control panels is at least the minimum clear distance given in Table S-2 away from such equipment.
1910.303(h)(4)(i)(C)
Where bare energized parts at any voltage or insulated energized parts above 600 volts, nominal, to ground are located adjacent to such entrance, they shall be suitably guarded.
1910.303(h)(4)(ii)
Permanent ladders or stairways shall be provided to give safe access to the working space around electric equipment installed on platforms, balconies, mezzanine floors, or in attic or roof rooms or spaces.
Related Code Sections
1910.303(h)(4) Electrical, Entrance and Access to Work Space
At least one entrance not less than 610 mm (24 in.) wide and 1.98 m (6.5 ft) high shall be provided to give access to the working space about ...
1910.302(b)(3) Electrical, Requirements Applicable Only to Installations Made After April 16, 1981
) -- Over 600 volts, nominal -- Entrance and access to work space
§ 1910.304(f)(1)(vii) and (f)(1)(viii) -- Overcurrent protection -- 600 volts, nominal ...
1910.303(g)(1)(iii) Electrical,
At least one entrance of sufficient area shall be provided to give access to the working space about electric equipment ...
1910.302(b) Electrical, Extent of Application
, 1981:
§ 1910.303(h)(4) -- Over 600 volts, nominal -- Entrance and access to work space
§ 1910.304(f)(1)(vii) and (f)(1)(viii) -- Overcurrent ...
1910.302 Electrical, Electric Utilization Systems
and utilization equipment installed after April 16, 1981:
§ 1910.303(h)(4) -- Over 600 volts, nominal -- Entrance and access to work space ...