1704.24.1.2 Enlargements or Additions to Existing System
JUMP TO FULL CODE CHAPTER
Where there is an enlargement that triggers a new standpipe system or there is an addition to an existing standpipe system, hydrostatic pressure tests of the entire system shall be performed for every 75 feet (22 860 mm) of additional height added to the system. The permit holder shall perform a final acceptance test of the completed system in accordance with the requirements of Section 901.5 of this code.
Related Code Sections
1704.24.1.2 Structural Tests and Special Inspections, Enlargements or Additions to Existing System
Where there is an enlargement that triggers a new standpipe system or there is an addition to an existing standpipe system, hydrostatic pressure ...
NYC Building Code 2014 > 17 Structural Tests and Special Inspections > 1704 Special Inspections > 1704.24 Standpipe System Special Inspection > 1704.24.1 Hydrostatic Pressure Testing > 1704.24.1.2 Enlargements or Additions to Existing System
1704.22.1.2 Structural Tests and Special Inspections, Enlargements or Additions to Existing System
Where there is an enlargement that triggers a new standpipe system or there is an addition to an existing standpipe system, hydrostatic pressure ...
NYC Building Code 2008 > 17 Structural Tests and Special Inspections > 1704 Special Inspections > 1704.22 Standpipe System Special Inspection > 1704.22.1 Hydrostatic Pressure Testing > 1704.22.1.2 Enlargements or Additions to Existing System
901.9.5.3 Fire Protection Systems, Additional Requirements for Enlargements of Buildings With Existing Standpipe Systems
Where the alteration involves the addition of stories to a building with an existing standpipe system, and one or more stair shafts are not currently ...
NYC Building Code 2014 > 9 Fire Protection Systems > 901 General > 901.9 Special Provisions for Prior Code Buildings > 901.9.5 Additional Provisions > 901.9.5.3 Additional Requirements for Enlargements of Buildings With Existing Standpipe Systems
401.4 Gas Piping Installations, Additional Appliances
served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be provided ...
401.4 Gas Piping Installations, Additional Appliances
served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be provided ...