// CODE SNIPPET
1206.2.10.3 Energy Management System
Go To Full Code Chapter
An approved energy management system shall be provided for battery technologies other than lead-acid and nickel cadmium for monitoring and balancing cell voltages, currents and temperatures within the manufacturer's specifications. The system shall transmit an alarm signal to an approved location if potentially hazardous temperatures or other conditions such as short circuits, over voltage or under voltage are detected.
Upcodes Diagrams
Related Code Sections
1206.3.4.3 Energy Systems, Energy Management System
An approved energy management system shall be provided for monitoring and balancing capacitor voltages, currents and temperatures within ...
Article 750 Special Conditions, Energy Management Systems
This article applies to the installation and operation of energy management systems. Informational Note: Performance provisions in other codes ...
750.50 Special Conditions, Field Markings
Where an energy management system is employed to control electrical power through the use of a remote means, a directory identifying the controlled ...
(A) Special Conditions, Load Shedding Controls
An energy management system shall not override the load shedding controls put in place to ensure the minimum electrical capacity for the following ...
(B) Special Conditions, Disconnection of Power
An energy management system shall not be permitted to cause disconnection of power to the following: Elevators, escalators, moving walks ...