26.6.3.8 End-to-End Communication Time for Alarm
Go To Full Code Chapter
The maximum duration between the initiation of an alarm signal at the protected premises, transmission of the signal, and subsequent display and recording of the alarm signal at the supervising station shall not exceed 90 seconds.