713.11 Enclosure at the Bottom
JUMP TO FULL CODE CHAPTER
Shafts that do not extend to the bottom of the building or structure shall comply with one of the following:
- They shall be enclosed at the lowest level with construction of the same fire-resistance rating as the lowest floor through which the shaft passes, but not less than the rating required for the shaft enclosure.
- They shall terminate in a room having a use related to the purpose of the shaft. The room shall be separated from the remainder of the building by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. The fire-resistance rating and opening protectives shall be not less than the protection required for the shaft enclosure.
- They shall be protected by approved fire dampers install ed in accordance with their listing at the lowest floor level within the shaft enclosure.
Exceptions:
- The fire-resistance-rated room separation is not required, provided there are no openings in or penetrations of the shaft enclosure to the interior of the building except at the bottom. The bottom of the shaft shall be closed off around the penetrating items with materials permitted by Section 718.3.1 for draftstopping, or the room shall be provided with an approved automatic sprinkler system.
- A shaft enclosure containing a waste or linen chute shall not be used for any other purpose and shall discharge in a room protected in accordance with Section 713.13.4.
- The fire-resistance-rated room separation and the protection at the bottom of the shaft are not required provided there are no combustibles in the shaft and there are no openings or other penetrations through the shaft enclosure to the interior of the building.
Related Code Sections
607.5.5.1 Duct Systems, Enclosure at the Bottom
Shaft enclosures that do not extend to the bottom of the building or structure shall be protected in accordance with Section 713.11 ...
Mechanical Code 2015 of New York State > 6 Duct Systems > 607 Duct and Transfer Openings > 607.5 Where Required > 607.5.5 Shaft Enclosures > 607.5.5.1 Enclosure at the Bottom
607.5.5.1 Duct Systems, Enclosure at the Bottom
Shaft enclosures that do not extend to the bottom of the building or structure shall be protected in accordance with Section 713.11 of the Building ...
2020 Mechanical Code of NYS > 6 Duct Systems > 607 Duct and Transfer Openings > 607.5 Where Required > 607.5.5 Shaft Enclosures > 607.5.5.1 Enclosure at the Bottom
707.11 Fire-Resistance-Rated Construction, Enclosure at the Bottom
Shafts that do not extend to the bottom of the building or structure shall:
Be enclosed at the lowest level with construction of the same fire ...
2010 Building Code of NY > 7 Fire-Resistance-Rated Construction > 707 Shaft Enclosures > 707.11 Enclosure at the Bottom
713.11 Fire and Smoke Protection Features, Enclosure at the Bottom
Shafts that do not extend to the bottom of the building or structure shall comply with one of the following: They shall be enclosed at the lowest ...
2020 Building Code of New York State > 7 Fire and Smoke Protection Features > 713 Shaft Enclosures > 713.11 Enclosure at the Bottom
713.11 Fire and Smoke Protection Features, Enclosure at the Bottom
Shafts that do not extend to the bottom of the building or structure shall comply with one of the following:
They shall be enclosed at the lowest ...
Building Code 2015 of New York State > 7 Fire and Smoke Protection Features > 713 Shaft Enclosures > 713.11 Enclosure at the Bottom