66.19.7.2.4 Emergency Venting
Go To Full Code Chapter
66.19.7.2.4.1
Cooking oil storage tanks shall be provided with
emergency relief venting in accordance with Section 66.22.
[30:19.7.2.4.1]
66.19.7.2.4.2*
For nonmetallic cooking oil storage tanks,
emergency relief venting by form of construction shall be
permitted. This shall include the low melting point of the
material of construction of the tank. [30:19.7.2.4.2]
66.19.7.2.4.3
For metallic cooking oil storage tanks, emergency relief venting by form of construction shall be prohibited. [30:19.7.2.4.3]
66.19.7.2.4.4
Emergency vents shall be permitted to discharge
inside the building. [30:19.7.2.4.4]
Upcodes Diagrams
Related Code Sections
66.19.7.2.4 Flammable and Combustible Liquids, Emergency Venting
Cooking oil storage tanks shall be provided with emergency relief venting in accordance with Section 66.22. [30:19.7.2.4.1 ...
66.19.7.2.4 Flammable and Combustible Liquids, Emergency Venting
Cooking oil storage tanks shall be provided with
emergency relief venting in accordance with Section 66.22.
[30:19.7.2.4.1 ...
66.22.7.3* Flammable and Combustible Liquids, Extension of Emergency Vent Piping
Piping to or
from approved emergency vent devices for atmospheric and
low-pressure tanks shall be sized to provide emergency vent
flows that limit ...
Fire Code 2021 of West Virginia > 66 Flammable and Combustible Liquids > 66.22 Storage of Ignitible (Flammable or Combustible) Liquids in Tanks — Aboveground Storage Tanks > 66.22.7 Emergency Relief Venting for Fire Exposure for Aboveground Storage Tanks > 66.22.7.3* Extension of Emergency Vent Piping
66.22.7.4* Flammable and Combustible Liquids, Extension of Emergency Vent Piping
Piping to or from approved emergency vent devices for atmospheric and low-pressure tanks shall be sized to provide emergency vent flows that limit ...
66.27.7.1.6* Flammable and Combustible Liquids, Extension of Emergency Vent Piping
Piping to or from approved emergency vents for atmospheric and low-pressure
tanks shall be sized to provide emergency vent flows
that limit the back ...