[M] 605.17.2 Emergency Ventilation System
JUMP TO FULL CODE CHAPTER
An emergency ventilation system shall be provided at the minimum exhaust rate specified in ASHRAE 15 or Table 605.17.2. Shut down of the emergency ventilation system shall be by manual means.
TABLE [M] 605.17.2
MINIMUM EXHAUST RATE
REFRIGERANT | Q (m3/sec) | Q (cfm) |
R32 | 15.4 | 32,600 |
R143a | 13.6 | 28,700 |
R444A | 6.46 | 13,700 |
R444B | 10.6 | 22,400 |
R445A | 7.83 | 16,600 |
R446A | 23.9 | 50,700 |
R447A | 23.8 | 50,400 |
R451A | 7.04 | 15,000 |
R451B | 7.05 | 15,000 |
R1234yf | 7.80 | 16,600 |
R1234ze(E) | 5.92 | 12,600 |
Related Code Sections
1106.5.2 Refrigeration, Emergency Ventilation System
An emergency ventilation system shall be provided at the minimum exhaust rate specified in ASHRAE 15 or Table 1106.5.2. Shutdown of the emergency ...
Mechanical Code 2018 of Kansas > 11 Refrigeration > 1106 Machinery Room, Special Requirements > 1106.5 Special Requirements for Group A2L Refrigerant Machinery Rooms > 1106.5.2 Emergency Ventilation System
605.17.2 Building Services and Systems, Emergency Ventilation System
An emergency ventilation system shall be provided at the minimum exhaust rate specified in ASHRAE 15 or Table 605.17.2. Shut down of the emergency ...
Fire Code 2018 of Kansas > 6 Building Services and Systems > 605 Mechanical Refrigeration > 605.17 Special Requirements for Group A2L Refrigerant Machinery Rooms > 605.17.2 Emergency Ventilation System
Section 1109 Refrigeration, Periodic Testing
and associated equipment intended to operate emergency ventilation systems. Detection and alarm systems ...
605.6.1 Building Services and Systems, Periodic Testing
Fans and associated equipment intended to operate emergency ventilation systems. Detection and alarm systems ...
Fire Code 2018 of Kansas > 6 Building Services and Systems > 605 Mechanical Refrigeration > 605.6 Testing of Equipment > 605.6.1 Periodic Testing
Section 1106 Refrigeration, Machinery Room, Special Requirements
activate at or below a refrigerant concentration of 25% of the LFL. Upon activation, the detection system shall activate the emergency ventilation ...