A dedicated twoway emergency communication phone system designed and installed in accordance with NFPA 72 shall be provided in all underground stations to facilitate direct communications for emergency response between remote locations and the EMP.
907.2.26.4.1
Remote emergency phones shall be located at ends of station platforms, each hose outlet connection and station valve rooms.
907.2.26.4.2
Provisions shall be made in the design of this two-way emergency communication phone system for extensions of the system to the next passenger station or guideway portal.