// CODE SNIPPET
313.7 Emergency Shutoff Switch
Go To Full Code Chapter
An emergency shutoff switch shall be provided to disconnect power to recirculation and jet system pumps and air blowers. Emergency shutoff switches shall be: provided with access; located within sight of the pool or spa; and located not less than 5 feet (1524 mm) horizontally from the inside walls of the pool or spa.
Exception: Onground storable pools, permanent inground residential swimming pools, residential spas and residential water features.
Upcodes Diagrams
Related Code Sections
313.7 General Compliance, Emergency Shutoff Switch
An emergency shutoff switch shall be provided to disconnect power to recirculation and jet system pumps and air blowers. Emergency shutoff switches ...
412.4 Public Swimming Pools, Emergency Shutoff Switch
Signs shall be posted that clearly indicate the location of the pump emergency shutoff switch. Such switch shall be clearly identified as the pump ...
504.1 Public Spas and Public Exercise Spas, Emergency Shutoff Switch
One emergency shutoff switch shall be provided to disconnect power to circulation and jet system pumps and air blowers. Emergency shutoff switches ...
802.2.1 Alterations - Level 3, Emergency Controls
with the following: Emergency shutoff switches for furnaces and boilers in basements shall be located at the top of the stairs leading ...
15.3.8.3 Acetylene Cylinder Charging Plants,
An emergency electrical shutoff switch shall be provided to shut off acetylene compressors and generators ...