New buildings shall have approved radio coverage for emergency responders within the building based on the existing coverage levels of the public safety communication systems utilized by the jurisdiction, measured at the exterior of the building. This section shall not require improvement of the existing public safety communication systems.
Exceptions:
  1. Where approved by the building official and the fire code official, a wired communication system in accordance with Section 907.2.12.2 shall be permitted to be installed or maintained instead of an approved radio coverage system.
  2. Where it is determined by the fire code official that the radio coverage system is not needed.
  3. In facilities where emergency responder radio coverage is required and such systems, components or equipment required could have a negative impact on the normal operations of that facility, the fire code official shall have the authority to accept an automatically activated emergency responder radio coverage system.

Related Code Sections

510.1 Fire Service Features, Emergency Responder Radio Coverage in New Buildings
New buildings shall have approved radio coverage for emergency responders within the building based on the existing coverage levels of the public ...
Section 915 Fire Protection Systems, Emergency Responder Radio Coverage
Emergency responder radio coverage shall be provided in all new buildings in accordance with Section 510 of the International Fire Code ...
Section 916 Fire Protection Systems, Emergency Responder Radio Coverage
Emergency responder radio coverage shall be provided in all new buildings in accordance with Section 510 of the International Fire Code ...
Section 918 Fire Protection and Life Safety Systems, Emergency Responder Radio Coverage
Emergency responder radio coverage shall be provided in all new buildings in accordance with Section 510 of the International Fire Code ...
Section 510 Fire Service Features, Emergency Responder Radio Coverage
All buildings shall have approved radio coverage for emergency responders within the building based upon the existing coverage levels of the public ...