53.2.1 Emergency Pressure Control System
JUMP TO FULL CODE CHAPTER
Each high and intermediate pressure zone in a refrigeration system shall be provided with a single automatic valve providing a crossover connection to a lower pressure zone. Automatic crossover valves shall comply with 53.2.1.1.1 through 53.2.1.1.4.
Operation of an automatic crossover valve shall cause all compressors on the affected system to immediately stop in accordance with the following:
- Dedicated pressure-sensing devices located immediately adjacent to crossover valves shall be permitted as a means for determining operation of a valve.
- To ensure that the automatic crossover valve system provides a redundant means of stopping compressors in an overpressure condition, high pressure cutout sensors associated with compressors shall not be used as a basis for determining operation of a crossover valve.
Activation of the overpressure sensing device shall cause all compressors on the affected system to immediately stop.
Related Code Sections
1105.9 Refrigeration, Emergency Pressure Control System
be provided with an emergency pressure control system in accordance with Section 606.10 of the NFPA Life Safety Code 2018 edition ...
Mechanical Code 2015 of West Virginia > 11 Refrigeration > 1105 Machinery Room, General Requirements > 1105.9 Emergency Pressure Control System
53.2.1 Mechanical Refrigeration, Emergency Pressure Control System
with an emergency pressure control system in accordance with 53.2.1.1 and 53.2.1.2 ...
Fire Code 2018 of West Virginia > 53 Mechanical Refrigeration > 53.2 Safety Features > 53.2.1 Emergency Pressure Control System
53.2.1.1.3 Mechanical Refrigeration, System Design Pressure
Refrigeration system zones that are connected to a higher pressure zone by an automatic crossover valve shall be designed to safely contain ...
Fire Code 2018 of West Virginia > 53 Mechanical Refrigeration > 53.2 Safety Features > 53.2.1 Emergency Pressure Control System > 53.2.1.1 High and Intermediate Pressure Zones > 53.2.1.1.3 System Design Pressure
53.2.1.1.1 Mechanical Refrigeration, Overpressure Limit Set Point for Crossover Valves
Automatic crossover valves shall be provided to automatically relieve excess system pressure to a lower pressure zone if the pressure in a high ...
Fire Code 2018 of West Virginia > 53 Mechanical Refrigeration > 53.2 Safety Features > 53.2.1 Emergency Pressure Control System > 53.2.1.1 High and Intermediate Pressure Zones > 53.2.1.1.1 Overpressure Limit Set Point for Crossover Valves