403.4.8.1 Emergency Power Loads in Occupancies Other Than R-2
JUMP TO FULL CODE CHAPTER
In buildings of any occupancy group other than Group R-2, the following are classified as emergency power loads:
- Exit signs and means of egress illumination required by Chapter 10;
- Elevator car lighting;
- Emergency voice/alarm communications systems, including Fire Department in-building Auxiliary Radio Communication systems (ARCs);
- Automatic fire detection systems;
- Fire alarm systems; and
- Electrically powered fire pumps, including manual fire pumps, automatic fire pumps, and sprinkler booster pumps.
Related Code Sections
403.11.1 Special Detailed Requirements Based on Use and Occupancy, Emergency Power Loads in Occupancies Other Than R-2
In buildings of any occupancy group other than Group R-2, the following are classified as emergency power loads: 1. Exit signs ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 403 High-Rise Buildings > 403.11 Emergency Power Systems > 403.11.1 Emergency Power Loads in Occupancies Other Than R-2
403.4.8.1 Special Detailed Requirements Based on Use and Occupancy, Emergency Power Loads in Occupancies Other Than R-2
In buildings of any occupancy group other than Group R-2, the following are classified as emergency power loads: Exit signs and means of egress ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 403 High-Rise Buildings > 403.4 Emergency Systems > 403.4.8 Emergency Power Systems > 403.4.8.1 Emergency Power Loads in Occupancies Other Than R-2
2702.4 Electrical, Required Loads for Optional Standby Power Systems
Group R-2 occupancies in buildings greater than 125 feet (38 100 mm) in height, at least one elevator serving all floors, or one elevator per bank ...
NYC Building Code 2014 > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.4 Required Loads for Optional Standby Power Systems
2702.4 Electrical, Required Loads for Optional Standby Power Systems
:
For Group R-2 occupancies in buildings greater than 125 feet (38 100 mm) in height, at least one elevator serving all floors ...
NYC Building Code 2008 > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.4 Required Loads for Optional Standby Power Systems
Section 403 Special Detailed Requirements Based on Use and Occupancy, High-Rise Buildings
In buildings of any occupancy group other than Group R-2, the following are classified ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 403 High-Rise Buildings