1104.5.1 Emergency Power Duration and Installation
JUMP TO FULL CODE CHAPTER
Emergency power for means of egress illumination shall be provided in accordance with Section 1203. In other than Group I-2, emergency power shall be provided for not less than 60 minutes for systems requiring emergency power.
Related Code Sections
1104.5.1 Construction Requirements for Existing Buildings, Emergency Power Duration and Installation
Emergency power for means of egress illumination shall be provided in accordance with Section 1203. In other than Group I-2, emergency power shall ...
Fire Code 2021 of Colorado > 11 Construction Requirements for Existing Buildings > 1104 Means of Egress for Existing Buildings > 1104.5 Illumination Emergency Power > 1104.5.1 Emergency Power Duration and Installation
1104.5.1 Construction Requirements for Existing Buildings, Emergency Power Duration and Installation
Emergency power for means of egress illumination shall be provided in accordance with Section 1203. In other than Group I-2, emergency power shall ...
Fire Code 2018 of Colorado > 11 Construction Requirements for Existing Buildings > 1104 Means of Egress for Existing Buildings > 1104.5 Illumination Emergency Power > 1104.5.1 Emergency Power Duration and Installation
1008.3.4 Means of Egress, Duration
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment ...
Building Code 2021 of Colorado > 10 Means of Egress > 1008 Means of Egress Illumination > 1008.3 Emergency Power for Illumination > 1008.3.4 Duration
1008.3.4 Means of Egress, Duration
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 10 Means of Egress > 1008 Means of Egress Illumination > 1008.3 Emergency Power for Illumination > 1008.3.4 Duration
1008.3.4 Means of Egress, Duration
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 10 Means of Egress > 1008 Means of Egress Illumination > 1008.3 Emergency Power for Illumination > 1008.3.4 Duration