1031.10 Emergency Lighting Equipment Inspection and Testing
JUMP TO FULL CODE CHAPTER
Emergency lighting shall be maintained in accordance with Section 1008 and shall be inspected and tested in
accordance with Sections 1031.10.1 and 1031.10.2.
Emergency lighting equipment shall be tested monthly for a duration of not less than 30 seconds. The test shall be performed manually or by an automated self-testing and self-diagnostic routine. Where testing is performed by self-testing and self-diagnostics, a visual inspection of the emergency lighting equipment shall be conducted monthly to identify any equipment displaying a trouble indicator or that has become damaged or otherwise impaired.
Battery-powered emergency lighting equipment shall be tested annually by operating the equipment on battery power for not less than 90 minutes.
Related Code Sections
1031.10 Means of Egress, Emergency Lighting Equipment Inspection and Testing
routine. Where testing is performed by self-testing and self-diagnostics, a visual inspection of the emergency lighting equipment shall be conducted monthly ...
California Fire Code 2019 > 10 Means of Egress > 1031 Maintenance of the Means of Egress > 1031.10 Emergency Lighting Equipment Inspection and Testing
604.6 Building Services and Systems, Emergency Lighting Equipment
Emergency lighting shall be inspected and tested in accordance with Sections 604.6.1 through 604.6.2.1 ...
California Fire Code 2016 > 6 Building Services and Systems > 604 Emergency and Standby Power Systems > 604.6 Emergency Lighting Equipment
3102F.3.5.3 [SLC] Marine Oil Terminals, Mechanical and Electrical Inspections
systems Pumps and pump systems Lighting Communications equipment Gangways Electrical switches and junction boxes Emergency power equipment Air ...
California Building Code 2016 (Vol 1 & 2) > 31F [SLC] Marine Oil Terminals > 3102F Audit and Inspection > 3102F.3 Audits > 3102F.3.5 Scope of Inspections > 3102F.3.5.3 Mechanical and Electrical Inspections
604.6.1 Building Services and Systems, Activation Test
An activation test of the emergency lighting equipment shall be completed monthly. The activation test shall ensure the emergency lighting activates ...
California Fire Code 2016 > 6 Building Services and Systems > 604 Emergency and Standby Power Systems > 604.6 Emergency Lighting Equipment > 604.6.1 Activation Test
1705A.13.3.1 Special Inspections and Tests, [OSHPD 1 & 4]
Special seismic certification shall be required for the following systems, equipment, and components: emergency and standby power systems ...
California Building Code 2016 (Vol 1 & 2) > 17A Special Inspections and Tests > 1705A Required Special Inspections and Tests > 1705A.13 Testing for Seismic Resistance > 1705A.13.3 Special Seismic Certification > 1705A.13.3.1 [OSHPD 1 & 4]