42.10.2.2.4 Emergency Fuel Shutoff
Go To Full Code Chapter
42.10.2.2.4.1
Emergency fuel shutoff control stations shall be
accessible at all times. [407:4.2.4.1]
42.10.2.2.4.2
A procedure shall be established to notify the
fire department serving the airport in the event of a control
station activation. [407:4.2.4.2]
42.10.2.2.4.3
42.10.2.2.4.4
The cause of the shutoff shall be identified and
corrected before fuel flow is resumed. [407:4.2.4.4]
42.10.2.2.4.5
42.10.2.2.4.6
Each individual device shall be checked at least
once during every 12-month period. [407:4.2.4.6]
42.10.2.2.4.7
Suitable records shall be kept of tests required
by this section. [407:4.2.4.7]