607.4 Emergency Elevator Operation and Maintenance
Go To Full Code Chapter
All elevators equipped with Phase I emergency recall operation and Phase II emergency in-car operation shall be maintained in proper working order such that the emergency elevator operations are operable at all times. All elevators with Phase I emergency recall operation shall be subjected, at least monthly, to a Phase I recall test. All elevators with Phase II emergency in-car operation shall be subjected, at least monthly, to a minimum of a one-floor operation II test.