Section 2702 Emergency and Standby Power Systems [F]

2010 Building Code of NY > 27 Electrical > 2702 Emergency and Standby Power Systems [F]
JUMP TO FULL CODE CHAPTER

2702.1 Installation

Emergency and standby power systems required by this code or the Fire Code of New York State shall be installed in accordance with this code, NFPA 110 and 111. [F]

2702.1.1 Stationary Generators

Emergency and standby power generators shall be listed in accordance with UL 2200. [F]

2702.2 Where Required

Emergency and standby power systems shall be provided where required by Sections 2702.2.1 through 2702.2.20. [F]

2702.2.1 Group a Occupancies

Emergency power shall be provided for voice communication systems in Group A occupancies in accordance with Section 907.2.1.2. [F]

2702.2.2 Smoke Control Systems

Standby power shall be provided for smoke control systems in accordance with Section 909.11. [F]

2702.2.3 Exit Signs

Emergency power shall be provided for exit signs in accordance with Section 1011.5.3. [F]

2702.2.4 Means of Egress Illumination

Emergency power shall be provided for means of egress illumination in accordance with Section 1006.3. [F]

2702.2.5 Accessible Means of Egress Elevators

Standby power shall be provided for elevators that are part of an accessible means of egress in accordance with Section 1007.4. [F]

2702.2.6 Accessible Means of Egress Platform Lifts

Standby power in accordance with this section or ASME A18.1 shall be provided for platform lifts that are part of an accessible means of egress in accordance with Section 1007.5. [F]

2702.2.7 Horizontal Sliding Doors

Standby power shall be provided for horizontal sliding doors in accordance with Section 1008.1.3.3. [F]

2702.2.8 Semiconductor Fabrication Facilities

Emergency power shall be provided for semiconductor fabrication facilities in accordance with Section 415.8.10. [F]

2702.2.9 Membrane Structures

Standby power shall be provided for auxiliary inflation systems in accordance with Section 3102.8.2. Emergency power shall be provided for exit signs in temporary tents and membrane structures in accordance with the Fire Code of New York State . [F]

2702.2.10 Hazardous Materials

Emergency or standby power shall be provided in occupancies with hazardous materials in accordance with Section 414.5.4. [F]

2702.2.11 Highly Toxic and Toxic Materials

Emergency power shall be provided for occupancies with highly toxic or toxic materials in accordance with the Fire Code of New York State . [F]

2702.2.12 Organic Peroxides

Standby power shall be provided for occupancies with silane gas in accordance with the Fire Code of New York State . [F]

2702.2.13 Pyrophoric Materials

Emergency power shall be provided for occupancies with silane gas in accordance with the Fire Code of New York State . [F]

2702.2.14 Covered Mall Buildings

Standby power shall be provided for voice/alarm communication systems in covered mall buildings in accordance with Section 402.13. [F]

2702.2.15 High-Rise Buildings

Emergency and standby power shall be provided in high-rise buildings in accordance with Sections 403.10 and 403.11. [F]

2702.2.16 Underground Buildings

Emergency and standby power shall be provided in underground buildings in accordance with Sections 405.9 and 405.10. [F]

2702.2.17 Group I-3 Occupancies

Emergency power shall be provided for doors in Group I-3 occupancies in accordance with Section 408.4.2. [F]

2702.2.18 Airport Traffic Control Towers

Standby power shall be provided in airport traffic control towers in accordance with Section 412.1.5. [F]

2702.2.19 Elevators

Standby power for elevators shall be provided as set forth in Section 3003.1. [F]

2702.2.20 Smokeproof Enclosures

Standby power shall be provided for smokeproof enclosures as required by Section 909.20. [F]

2702.3 Maintenance

Emergency and standby power systems shall be maintained and tested in accordance with the Fire Code of New York State. [F]
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


Section 2702 Electrical, Emergency and Standby Power Systems [F]
] Emergency and standby power systems shall be provided where required by Sections 2702.2.1 through 2702.2.20. [F ...
2010 Building Code of NY > 27 Electrical > 2702 Emergency and Standby Power Systems [F]
2702.2.10 Electrical, Hazardous Materials
Emergency or standby power shall be provided in occupancies with hazardous materials in accordance with Section 414.5.4. [F] ...
2010 Building Code of NY > 27 Electrical > 2702 Emergency and Standby Power Systems [F] > 2702.2 Where Required > 2702.2.10 Hazardous Materials
2702.2.16 Electrical, Underground Buildings
Emergency and standby power shall be provided in underground buildings in accordance with Sections 405.9 and 405.10. [F] ...
2010 Building Code of NY > 27 Electrical > 2702 Emergency and Standby Power Systems [F] > 2702.2 Where Required > 2702.2.16 Underground Buildings
2702.2.15 Electrical, High-Rise Buildings
Emergency and standby power shall be provided in high-rise buildings in accordance with Sections 403.10 and 403.11. [F] ...
2010 Building Code of NY > 27 Electrical > 2702 Emergency and Standby Power Systems [F] > 2702.2 Where Required > 2702.2.15 High-Rise Buildings
2702.2.19 Electrical, Elevators
Standby power for elevators shall be provided as set forth in Section 3003.1. [F] ...
2010 Building Code of NY > 27 Electrical > 2702 Emergency and Standby Power Systems [F] > 2702.2 Where Required > 2702.2.19 Elevators
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US