Section 2702 Emergency and Standby Power Systems

Jump To Full Code Chapter
[F] 2702.1 General
Emergency power systems and standby power systems shall comply with Sections 2702.1.1 through 2702.1.8.
[F] 2702.1.1 Stationary Generators
Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200.
[F] 2702.1.2 Fuel-Line Piping Protection
Fuel lines supplying a generator set inside a high-rise building shall be separated from areas of the building other than the room the generator is located in by one of the following methods:
  1. A fire-resistant pipe-protection system that has been tested in accordance with UL 1489. The system shall be installed as tested and in accordance with the manufacturer's installation instructions, and shall have a rating of not less than 2 hours. Where the building is protected throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1, the required rating shall be reduced to 1 hour.
  2. An assembly that has a fire-resistance rating of not less than 2 hours. Where the building is protected throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1, the required fire-resistance rating shall be reduced to 1 hour.
  3. Other approved methods.
[F] 2702.1.3 Installation
Emergency power systems and standby power systems required by this code or the International Fire Code shall be installed in accordance with the International Fire Code, NFPA 70, NFPA 110 and NFPA 111.
[F] 2702.1.4 Load Transfer
Emergency power systems shall automatically provide secondary power within 10 seconds after primary power is lost, unless specified otherwise in this code. Standby power systems shall automatically provide secondary power within 60 seconds after primary power is lost, unless specified otherwise in this code.
[F] 2702.1.5 Load Duration
Emergency power systems and standby power systems shall be designed to provide the required power for a minimum duration of 2 hours without being refueled or recharged, unless specified otherwise in this code.
[F] 2702.1.6 Uninterruptable Power Source
An uninterrupted source of power shall be provided for equipment where required by the manufacturer's instructions, the listing, this code or applicable referenced standards.
[F] 2702.1.7 Interchangeability
Emergency power systems shall be an acceptable alternative for installations that require standby power systems.
[F] 2702.1.8 Group I-2 Occupancies
In Group I-2 occupancies located in flood hazard areas established in Section 1612.3, where new essential electrical systems are installed, and where new essential electrical system generators are installed, the systems and generators shall be located and installed in accordance with ASCE 24. Where connections for hookup of temporary generators are provided, the connections shall be located at or above the elevation required in ASCE 24.
[F] 2702.2 Where Required
Emergency and standby power systems shall be provided where required by Sections 2702.2.1 through 2702.2.19.
[F] 2702.2.1 Ambulatory Care Facilities
Essential electrical systems for ambulatory care facilities shall comply with Section 422.6.
[F] 2702.2.2 Elevators and Platform Lifts
Standby power shall be provided for elevators and platform lifts as required in Sections 1009.4.1, 1009.5, 3003.1, 3007.8 and 3008.8.
[F] 2702.2.3 Emergency Responder Communication Coverage Systems
Standby power shall be provided for in-building 2-way emergency responder communication coverage systems required in Section 918 and the International Fire Code. The standby power supply shall be capable of operating the in-building 2-way emergency responder communication coverage system at 100-percent system operation capacity for a duration of not less than 12 hours.
[F] 2702.2.4 Emergency Voice/Alarm Communication Systems
Standby power shall be provided for emergency voice/alarm communication systems in accordance with NFPA 72.
[F] 2702.2.5 Exhaust Systems
Standby power shall be provided for common exhaust systems for domestic kitchens located in multistory structures as required in Section 505.5 of the International Mechanical Code. Standby power shall be provided for common exhaust systems for clothes dryers located in multistory structures as required in Section 504.11 of the International Mechanical Code and Section 614.11 of the International Fuel Gas Code.
[F] 2702.2.6 Exit Signs
Emergency power shall be provided for exit signs as required in Section 1013.6.3. The system shall be capable of powering the required load for a duration of not less than 90 minutes.
[F] 2702.2.7 Gas Detection System
Emergency or standby power shall be provided for gas detection systems in accordance with the International Fire Code.
[F] 2702.2.8 Group I-2 Occupancies
Essential electrical systems for Group I-2 occupancies shall be in accordance with Section 407.11.
[F] 2702.2.9 Group I-3 Occupancies
Emergency power shall be provided for power-operated doors and locks in Group I-3 occupancies as required in Section 408.4.2.
[F] 2702.2.10 Hazardous Materials
Emergency or standby power shall be provided in occupancies with hazardous materials where required by the International Fire Code.
[F] 2702.2.11 High-Rise Buildings
Emergency and standby power shall be provided in high-rise buildings as required in Section 403.4.8.
[F] 2702.2.12 Hydrogen Fuel Gas Rooms
Standby power shall be provided for hydrogen fuel gas rooms as required by the International Fire Code.
[F] 2702.2.13 Laboratory Suites
Standby or emergency power shall be provided in accordance with Section 5004.7 of the International Fire Code where laboratory suites are located above the sixth story above grade plane or located in a story below grade plane.
[F] 2702.2.14 Means of Egress Illumination
Emergency power shall be provided for means of egress illumination as required in Section 1008.3. The system shall be capable of powering the required load for a duration of not less than 90 minutes.
[F] 2702.2.15 Membrane Structures
Standby power shall be provided for auxiliary inflation systems in permanent membrane structures as required in Section 3102.8.2. Standby power shall be provided for a duration of not less than 4 hours. Auxiliary inflation systems in temporary air-supported and air-inflated membrane structures shall be provided in accordance with Section 3103.10.4 of the International Fire Code.
[F] 2702.2.16 Semiconductor Fabrication Facilities
Emergency power shall be provided for semiconductor fabrication facilities as required in Section 415.11.11.
[F] 2702.2.17 Smoke Control Systems
Standby power shall be provided for smoke control systems as required in Sections 404.7, 909.11, 909.20.7.2 and 909.21.5.
[F] 2702.2.18 Special Purpose Horizontal Sliding, Accordion or Folding Doors
Standby power shall be provided for special purpose horizontal sliding, accordion or folding doors as required in Section 1010.3.3. The standby power supply shall have a capacity to operate not fewer than 50 closing cycles of the door.
[F] 2702.2.19 Underground Buildings
Emergency and standby power shall be provided in underground buildings as required in Section 405.
[F] 2702.3 Critical Circuits
Required critical circuits shall be protected using one of the following methods:
  1. Cables, used for survivability of required critical circuits, that are listed in accordance with UL 2196 and have a fire-resistance rating of not less than 1 hour.
  2. Electrical circuit protective systems having a fire-resistance rating of not less than 1 hour. Electrical circuit protective systems are installed in accordance with their listing requirements.
  3. Construction having a fire-resistance rating of not less than 1 hour.
[F] 2702.4 Maintenance
Emergency and standby power systems shall be maintained and tested in accordance with the International Fire Code.

Related Code Sections

Section 2702 Electrical, Emergency and Standby Power Systems
Emergency power systems and standby power systems shall comply with Sections 2702.1.1 through 2702.1.8 ...
Section 2702 Electrical, Emergency and Standby Power Systems
Emergency power systems and standby power systems shall comply with Sections 2702.1.1 through 2702.1.8 ...
2.27.2 Electric Elevators, Emergency or Standby Power System
Elevators provided with an emergency or standby power system to operate the elevator in case the normal power supply fails shall comply ...