[F] 415.5 Emergency Alarms
JUMP TO FULL CODE CHAPTER
Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as set forth herein.
An approved manual emergency alarm system shall be provided in buildings, rooms or areas used for storage of hazardous materials. Emergency alarm-initiating devices shall be installed outside of each interior exit or exit access door of storage buildings, rooms or areas. Activation of an emergency alarm-initiating device shall sound a local alarm to alert occupants of an emergency situation involving hazardous materials.
Where hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 are transported through corridors, interior exit stairways or ramps, or exit passageways, there shall be an emergency telephone system, a local manual alarm station or an approved alarm-initiating device at not more than 150-foot (45 720 mm) intervals and at each exit and exit access doorway throughout the transport route. The signal shall be relayed to an approved central, proprietary or remote station service or constantly attended on-site location and shall initiate a local audible alarm.
Emergency alarm systems shall be supervised by an approved central, proprietary or remote station service or shall initiate an audible and visual signal at a constantly attended on-site location.
Emergency alarm systems shall be provided with emergency power in accordance with Section 2702.
Related Code Sections
414.7 Special Detailed Requirements Based on Use and Occupancy, Emergency Alarms
Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as set forth herein ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 414 Hazardous Materials > 414.7 Emergency Alarms
415.5 Special Detailed Requirements Based on Use and Occupancy, Emergency Alarms
Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as set forth herein ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.5 Emergency Alarms
415.5 Special Detailed Requirements Based on Occupancy and Use, Emergency Alarms
Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as set forth herein ...
2020 FBC - Building, 7th edition > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.5 Emergency Alarms
2702.2.1 Electrical, Emergency Alarm Systems
Emergency power shall be provided for emergency alarm systems as required by Section 415.5 ...
2017 FBC - Building, 6th edition > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.2 Where Required > 2702.2.1 Emergency Alarm Systems
415.10.3.5 Special Detailed Requirements Based on Use and Occupancy, Emergency Alarm System
Emergency alarm systems shall be provided in accordance with this section and Sections 414.7.1 and 414.7.2. The maximum allowable quantity per ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.10 Group H-5 > 415.10.3 Service Corridors > 415.10.3.5 Emergency Alarm System