[F] 415.11.3.5 Emergency Alarm System
JUMP TO FULL CODE CHAPTER
Emergency alarm systems shall be provided in accordance with this section and Sections 415.5.1 and 415.5.2. The maximum allowable quantity per control area provisions shall not apply to emergency alarm systems required for HPM.
An emergency alarm system shall be provided in service corridors, with not fewer than one alarm device in each service corridor.
Emergency alarms for corridors, interior exit stairways and ramps and exit passageways shall comply with Section 415.5.2.
Emergency alarms for liquid storage rooms, HPM rooms and gas rooms shall comply with Section 415.5.1.
An approved emergency telephone system, local alarm manual pull stations, or other approved alarm-initiating devices are allowed to be used as emergency alarm-initiating devices.
Activation of the emergency alarm system shall sound a local alarm and transmit a signal to the emergency control station.
Related Code Sections
415.11.3.5 Special Detailed Requirements Based on Occupancy and Use, Emergency Alarm System
Emergency alarm systems shall be provided in accordance with this section and Sections 415.5.1 and 415.5.2. The maximum allowable quantity per ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.11 Group H-5 > 415.11.3 Service Corridors > 415.11.3.5 Emergency Alarm System
Section 908 Fire Protection and Life Safety Systems, Emergency Alarm Systems
Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided in accordance with Section ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 908 Emergency Alarm Systems
415.11.3.5.5 Special Detailed Requirements Based on Occupancy and Use, Alarm Signals
Activation of the emergency alarm system shall sound a local alarm and transmit a signal to the emergency control station ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.11 Group H-5 > 415.11.3 Service Corridors > 415.11.3.5 Emergency Alarm System > 415.11.3.5.5 Alarm Signals
415.11.9.3 Special Detailed Requirements Based on Occupancy and Use, Signals
The emergency control station shall receive signals from emergency equipment and alarm and detection systems. Such emergency equipment and alarm ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.11 Group H-5 > 415.11.9 Emergency Control Station > 415.11.9.3 Signals
415.11.3 Special Detailed Requirements Based on Occupancy and Use, Service Corridors
Emergency alarm systems shall be provided in accordance ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.11 Group H-5 > 415.11.3 Service Corridors