704.8 Embedments and Enclosures
JUMP TO FULL CODE CHAPTER
Pipes, wires, conduits, ducts or other service facilities shall not be embedded in the required fire protection of a structural member that is required to be individually encased.
Exception: Pipes, wires, and conduits may be installed in the space between the required fire protection and the structural member protected, provided that where such facilities pierce the required fire protection:
Exception: Pipes, wires, and conduits may be installed in the space between the required fire protection and the structural member protected, provided that where such facilities pierce the required fire protection:
- the area of the penetration does not exceed two percent of the area of the fire protection on any one face,
- the penetrations are closed off with close-fitting metal escutcheons or plates, and
- the concealed space is firestopped at each story.
Related Code Sections
704.8 Fire and Smoke Protection Features, Embedments and Enclosures
Pipes, wires, conduits, ducts or other service facilities shall not be embedded in the required fire protection of a structural member ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 704 Fire-Resistance Rating of Structural Members > 704.8 Embedments and Enclosures
714.3 Fire-Resistance-Rated Construction, Embedments and Enclosures
Pipes, wires, conduits, ducts or other service facilities shall not be embedded in the required fire protection of a structural member ...
NYC Building Code 2008 > 7 Fire-Resistance-Rated Construction > 714 Fire-Resistance Rating of Structural Members > 714.3 Embedments and Enclosures
§27-324 Fire Protection Construction Requirements, Protection of Structural Members
-resistance rating. (a) Embedments and enclosures. Pipes, wires, conduits, ducts, or other service facilities shall not be embedded in the required ...
NYC 1968 Code (Vol I) > 5 Fire Protection Construction Requirements > 3 Fire-Resistance Requirements > §27-324 Protection of Structural Members
721.5.1.1.2 Fire and Smoke Protection Features, Embedments
shall not be embedded in any required fire-resistant materials ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 721 Calculated Fire Resistance > 721.5 Steel Assemblies > 721.5.1 Structural Steel Columns > 721.5.1.1 General > 721.5.1.1.2 Embedments
721.5.1.1.2 Fire-Resistance-Rated Construction, Embedments
shall not be embedded in any required fire-resistant materials ...
NYC Building Code 2008 > 7 Fire-Resistance-Rated Construction > 721 Calculated Fire Resistance > 721.5 Steel Assemblies > 721.5.1 Structural Steel Columns > 721.5.1.1 General > 721.5.1.1.2 Embedments