1910.306(c) Elevators, Dumbwaiters, Escalators, Moving Walks, Wheelchair Lifts, and Stairway Chair Lifts
Go To Full Code Chapter
The following requirements apply to elevators, dumbwaiters, escalators, moving walks, wheelchair lifts, and stairway chair lifts.
1910.306(c)(1) Disconnecting Means
Elevators, dumbwaiters, escalators, moving walks, wheelchair lifts, and stairway chair lifts shall have a single means for disconnecting all ungrounded main power supply conductors for each unit.
1910.306(c)(2) Control Panels
Control panels not located in the same space as the drive machine shall be located in cabinets with doors or panels capable of being locked closed.
1910.306(c)(3) Type
The disconnecting means shall be an enclosed externally operable fused motor circuit switch or circuit breaker capable of being locked in the open position. The disconnecting means shall be a listed device.
1910.306(c)(4) Operation
No provision may be made to open or close this disconnecting means from any other part of the premises. If sprinklers are installed in hoistways, machine rooms, or machinery spaces, the disconnecting means may automatically open the power supply to the affected elevators prior to the application of water. No provision may be made to close this disconnecting means automatically (that is, power may only be restored by manual means).
1910.306(c)(5) Location
The disconnecting means shall be located where it is readily accessible to qualified persons.
1910.306(c)(5)(i)
On elevators without generator field control, the disconnecting means shall be located within sight of the motor controller. Driving machines or motion and operation controllers not within sight of the disconnecting means shall be provided with a manually operated switch installed in the control circuit adjacent to the equipment in order to prevent starting. Where the driving machine is located in a remote machinery space, a single disconnecting means for disconnecting all ungrounded main power supply conductors shall be provided and be capable of being locked in the open position.
1910.306(c)(5)(iii)
On escalators and moving walks, the disconnecting means shall be installed in the space where the controller is located.
1910.306(c)(5)(iv)
On wheelchair lifts and stairway chair lifts, the disconnecting means shall be located within sight of the motor controller.
1910.306(c)(5)(ii)
On elevators with generator field control, the disconnecting means shall be located within sight of the motor controller for the driving motor of the motor-generator set. Driving machines, motor-generator sets, or motion and operation controllers not within sight of the disconnecting means shall be provided with a manually operated switch installed in the control circuit to prevent starting. The manually operated switch shall be installed adjacent to this equipment. Where the driving machine or the motor-generator set is located in a remote machinery space, a single means for disconnecting all ungrounded main power supply conductors shall be provided and be capable of being locked in the open position.
1910.306(c)(6) Identification and Signs
1910.306(c)(6)(i)
Where there is more than one driving machine in a machine room, the disconnecting means shall be numbered to correspond to the identifying number of the driving machine that they control.
1910.306(c)(6)(ii)
The disconnecting means shall be provided with a sign to identify the location of the supply-side overcurrent protective device.
1910.306(c)(7) Single-Car and Multicar Installations
On single-car and multicar installations, equipment receiving electrical power from more than one source shall be provided with a disconnecting means for each source of electrical power. The disconnecting means shall be within sight of the equipment served.
1910.306(c)(8) Warning Sign for Multiple Disconnecting Means
A warning sign shall be mounted on or next to the disconnecting means where multiple disconnecting means are used and parts of the controllers remain energized from a source other than the one disconnected. The sign shall be clearly legible and shall read "WARNING -- PARTS OF THE CONTROLLER ARE NOT DEENERGIZED BY THIS SWITCH."
1910.306(c)(9) Interconnection Between Multicar Controllers
A warning sign worded as required in paragraph (c)(8) of this section shall be mounted on or next to the disconnecting means where interconnections between controllers are necessary for the operation of the system on multicar installations that remain energized from a source other than the one disconnected.
1910.306(c)(10) Motor Controllers
Motor controllers may be located outside the spaces otherwise required by paragraph (c) of this section, provided they are in enclosures with doors or removable panels capable of being locked closed and the disconnecting means is located adjacent to or is an integral part of the motor controller. Motor controller enclosures for escalators or moving walks may be located in the balustrade on the side located away from the moving steps or moving treadway. If the disconnecting means is an integral part of the motor controller, it shall be operable without opening the enclosure.
Upcodes Diagrams
Related Code Sections
1910.306(c) Electrical, Elevators, Dumbwaiters, Escalators, Moving Walks, Wheelchair Lifts, and Stairway Chair Lifts
The following requirements apply to elevators, dumbwaiters, escalators, moving walks, wheelchair lifts, and stairway chair lifts ...
1910.302(b)(4) Electrical, Requirements Applicable Only to Installations Made After August 13, 2007
-- Disconnecting means
§ 1910.306(c)(4) -- Elevators, dumbwaiters, escalators, moving walks, wheelchair lifts, and stairway chair lifts -- Operation ...
1910.306(c)(3) Electrical, Type
The disconnecting means shall be an enclosed externally operable fused motor circuit switch or circuit breaker capable of being locked in the open ...
1910.306(c)(6) Electrical, Identification and Signs
Where there is more than one driving machine in a machine room, the disconnecting means shall be numbered to correspond to the identifying number ...
1910.306(c)(7) Electrical, Single-Car and Multicar Installations
On single-car and multicar installations, equipment receiving electrical power from more than one source shall be provided with a disconnecting means ...