(E) Elevation of Unguarded Live Parts
Go To Full Code Chapter
Unguarded live parts above working space shall be maintained at elevations not less than required by Table 110.34(E).
Table 110.34(E) Elevation of Unguarded Live Parts Above Working Space
Nominal Voltage Between Phases | Elevation | |
---|---|---|
m | ft | |
1001—7500V | 2.7 | 9 |
7501—35,000 V | 2.9 | 9 ft 6 in. |
Over 35 kV | Add 9.5 mm per kV above 35 kV | Add 0.37 in. per kV above 35 kV |