G307.5 Elevation of Certain Tanks and Containers Serving Critical Facilities
JUMP TO FULL CODE CHAPTER
The following tanks and containers shall be located at or above the design flood elevation specified in ASCE 24, Table 7-1, unless such tanks and containers serve buildings that include I-2 occupancies that are hospitals, in which case such tanks and containers shall be located at or above the greater of (i) the design flood elevation specified in ASCE 24, Table 7-1, or (ii) the 500-year flood elevation. Such tanks and containers must be designed to maintain service to such structure during flood conditions and shall comply with section 9.6 of ASCE 24;
- Medical and compressed gas storage tanks, oxygen tanks, and other cryogenic system storage tanks;
- Hazardous material storage tanks;
- Stationary compressed gas containers;
- Stationary cryogenic containers; and
- Stationary flammable gas storage containers.
Related Code Sections
G307.5 Flood-Resistant Construction, Elevation of Certain Tanks and Containers Serving Critical Facilities
The following tanks and containers shall be located at or above the design flood elevation specified in ASCE 24, Table 7-1, unless such tanks ...
NYC Building Code 2014 > G Flood-Resistant Construction > G307 Tanks > G307.5 Elevation of Certain Tanks and Containers Serving Critical Facilities
1109.6 Accessibility, Elevators
, serves not more than three contiguous levels, and elevators are not otherwise required by Chapter 30 ...
Section G307 Flood-Resistant Construction, Tanks
of the contents of the tanks during conditions of flooding to the design flood elevation, in accordance with ASCE 24; and Anchored to prevent lateral ...
1109.6 Accessibility, Elevators
feet (929 m 2 ) provided such LULA elevator serves not more than three contiguous floors and elevators are not otherwise required by Chapter 30 ...
Article 14 Elevators [PDF] (page 53)
to the pressure tank of a hydraulic elevator shall be equipped with a relief valve. Such valve shall be so installed that it cannot be shut off. Such ...