AJ501.5 Electrical Equipment and Wiring
JUMP TO FULL CODE CHAPTER
Service to the dwelling unit
shall be not less than 100 ampere, three-wire capacity and
service equipment shall be dead front having no live parts
exposed that could allow accidental contact. Type "S"
fuses shall be installed where fused equipment is used.
Exception: Existing service of 60 ampere, three-wire
capacity, and feeders of 30 ampere or larger two- or
three-wire capacity shall be accepted if adequate for the
electrical load being served.
Where
the work area includes any of the following areas within a
dwelling unit, the requirements of Sections AJ501.5.3.1
through AJ501.5.3.5 shall apply.
Not less than one lighting
outlet shall be provided in every bathroom, hallway,
stairway, attached garage and detached garage
with electric power to illuminate outdoor entrances and
exits, and in utility rooms and basements where these
spaces are used for storage or contain equipment requiring
service.
Related Code Sections
AJ501.5 Existing Building and Structures, Electrical Equipment and Wiring
Newly installed electrical
equipment and wiring relating to work done in any
work area shall comply with the materials and methods
requirements ...
2015 Michigan Residential Code > J Existing Building and Structures > AJ501 Alterations > AJ501.5 Electrical Equipment and Wiring
AJ501.5.3.4 Existing Building and Structures, Lighting Outlets
Not less than one lighting
outlet shall be provided in every bathroom, hallway,
stairway, attached garage and detached garage
with electric power ...
2015 Michigan Residential Code > J Existing Building and Structures > AJ501 Alterations > AJ501.5 Electrical Equipment and Wiring > AJ501.5.3 Additional Electrical Requirements > AJ501.5.3.4 Lighting Outlets
AJ501.5.3.1 Existing Building and Structures, Enclosed Areas
Enclosed areas other than
closets, kitchens, basements , garages, hallways, laundry
areas and bathrooms shall have not less than two
duplex ...
2015 Michigan Residential Code > J Existing Building and Structures > AJ501 Alterations > AJ501.5 Electrical Equipment and Wiring > AJ501.5.3 Additional Electrical Requirements > AJ501.5.3.1 Enclosed Areas
AJ501.5.3.3 Existing Building and Structures, Ground-Fault Circuit-Interruption
Ground-fault circuit-interruption shall be provided on
newly installed receptacle outlets if required by Chapters
34 through 43 ...
2015 Michigan Residential Code > J Existing Building and Structures > AJ501 Alterations > AJ501.5 Electrical Equipment and Wiring > AJ501.5.3 Additional Electrical Requirements > AJ501.5.3.3 Ground-Fault Circuit-Interruption
808.1 Alterations — Level 2, New Installations
All newly installed electrical equipment
and wiring relating to work done in any work area shall
comply with all applicable requirements of NFPA 70 ...
2015 Michigan Rehabilitation Code > 8 Alterations — Level 2 > 808 Electrical > 808.1 New Installations