// CODE SNIPPET
43.1.4.3 Electrical Devices in Spray Areas
Go To Full Code Chapter
43.1.4.3.1
The spray area as defined in 3.3.14.12 shall be
Class I, Division 1; Class I, Zone 1; Class II, Division 1; or Zone
21, whichever is applicable. [33:6.4.1]
43.1.4.3.2
Electrical wiring and utilization equipment that is
located in the spray area and is not subject to deposits of
combustible residues shall be suitable for Class I, Division 1;
Class I, Zone 1; Class II, Division 1; or Zone 21 locations, whichever is applicable. [33:6.4.2]
43.1.4.3.3*
Electrical wiring and utilization equipment that is
located in the spray area and is subject to deposits of combustible residues shall be listed for such exposure and shall be suitable for Class I, Division 1; Class I, Zone 1; Class II, Division 1; or
Zone 21 locations, whichever is applicable. [33:6.4.3]
Related Code Sections
43.1.4.3 Spraying, Dipping, and Coating Using Flammable or Combustible Materials, Electrical Devices in Spray Areas
] Electrical wiring and utilization equipment that is
located in the spray area and is subject to deposits of combustible ...
43.1.4.3 Spraying, Dipping, and Coating Using Flammable or Combustible Materials, Electrical Devices in Spray Areas
] Electrical wiring and utilization equipment that is located in the spray area and is subject to deposits of combustible ...
43.1.4.3.3* Spraying, Dipping, and Coating Using Flammable or Combustible Materials,
Electrical wiring and utilization equipment that is located in the spray area and is subject to deposits of combustible residues shall be listed ...
43.1.4.4 Spraying, Dipping, and Coating Using Flammable or Combustible Materials, Electrical Devices in Areas Adjacent to or Connected to Spray Areas
Electrical wiring and utilization equipment
located in areas adjacent to or connected to the spray area,
including but not limited to vestibules ...
43.1.4.4 Spraying, Dipping, and Coating Using Flammable or Combustible Materials, Electrical Devices in Areas Adjacent to or Connected to Spray Areas
Electrical wiring and utilization equipment located in areas adjacent to or connected to the spray area, including but not limited to vestibules ...