6.4.3.11.2 Electric-Motor-Driven Chiller System Recording and Reporting
Go To Full Code Chapter
The electrical energy use efficiency shall be trended every 15 minutes and graphically displayed and include hourly, daily, monthly, and annual data. The system shall maintain all data collected for a minimum of 36 months.