1006.2 Egress From Spaces

Building Code 2015 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress From Spaces
JUMP TO FULL CODE CHAPTER
Rooms, areas or spaces, including mezzanines, within a story or basement shall be provided with the number of exits or access to exits in accordance with this section.

1006.2.1 Egress Based on Occupant Load and Common Path of Egress Travel Distance

Two exits or exit access doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1.

Exceptions:

1. In Group R-2 and R-3 occupancies, one means of egress is permitted within and from individual dwelling units with a maximum occupant load of 20 where the dwelling unit is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and the common path of egress travel does not exceed 125 feet (38 100 mm).

2. Care suites in Group I-2 occupancies complying with Section 407.4.

TABLE 1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY

OCCUPANCY MAXIMUM OCCUPANT
LOAD OF SPACE
MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE (feet)
Without Sprinkler System
(feet)
With Sprinkler System
(feet)
Occupant Load
OL ≤ 30 OL > 30
Ac, E, M 49 75 75 75a
B 49 100 75 100a
F 49 75 75 100a
H-1, H-2, H-3 3 NP NP 25b
H-4, H-5 10 NP NP 75b
I-1, I-2d, I-4 10 NP NP 75a
I-3 10 NP NP 100a
R-1 10 NP NP 75a
R-2 10 NP NP 125a
R-3e 10 NP NP 125a
R-4e 10 75 75 125a
Sf 29 100 75 100a
U 49 100 75 75a

For SI: 1 foot = 304.8 mm.
NP = Not Permitted.
a. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.2.
b. Group H occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.2.5.
c. For a room or space used for assembly purposes having fixed seating, see Section 1029.8.
d. For the travel distance limitations in Group I-2, see Section 407.4.
e. The length of common path of egress travel distance in a Group R-3 occupancy located in a mixed occupancy building or within a Group R-3 or R-4 congregate living facility.
f. The length of common path of egress travel distance in a Group S-2 open parking garage shall be not more than 100 feet.

1006.2.1.1 Three or More Exits or Exit Access Doorways

Three exits or exit access doorways shall be provided from any space with an occupant load of 501 to 1,000. Four exits or exit access doorways shall be provided from any space with an occupant load greater than 1,000.

1006.2.2 Egress Based on Use

The numbers of exits or access to exits shall be provided in the uses described in Sections 1006.2.2.1 through 1006.2.2.5.

1006.2.2.1 Boiler, Incinerator and Furnace Rooms

Two exit access doorways are required in boiler, incinerator and furnace rooms where the area is over 500 square feet (46 m2) and any fuel-fired equipment exceeds 400,000 British thermal units (Btu) (422 000 KJ) input capacity. Where two exit access doorways are required, one is permitted to be a fixed ladder or an alternating tread device. Exit access doorways shall be separated by a horizontal distance equal to one-half the length of the maximum overall diagonal dimension of the room.

1006.2.2.2 Refrigeration Machinery Rooms

Machinery rooms larger than 1,000 square feet (93 m2) shall have not less than two exits or exit access doorways. Where two exit access doorways are required, one such doorway is permitted to be served by a fixed ladder or an alternating tread device. Exit access doorways shall be separated by a horizontal distance equal to one-half the maximum horizontal dimension of the room.

All portions of machinery rooms shall be within 150 feet (45 720 mm) of an exit or exit access doorway. An increase in exit access travel distance is permitted in accordance with Section 1017.1.

Doors shall swing in the direction of egress travel, regardless of the occupant load served. Doors shall be tight fitting and self-closing.

1006.2.2.3 Refrigerated Rooms or Spaces

Rooms or spaces having a floor area larger than 1,000 square feet (93 m2), containing a refrigerant evaporator and maintained at a temperature below 68°F (20°C), shall have access to not less than two exits or exit access doorways.

Exit access travel distance shall be determined as specified in Section 1017.1, but all portions of a refrigerated room or space shall be within 150 feet (45 720 mm) of an exit or exit access doorway where such rooms are not protected by an approved automatic sprinkler system. Egress is allowed through adjoining refrigerated rooms or spaces.

Exception: Where using refrigerants in quantities limited to the amounts based on the volume set forth in the International Mechanical Code.

1006.2.2.4 Day Care Means of Egress

Day care facilities, rooms or spaces where care is provided for more than 10 children that are 21/2 years of age or less, shall have access to not less than two exits or exit access doorways.

1006.2.2.5 Vehicular Ramps

Vehicular ramps shall not be considered as an exit access ramp unless pedestrian facilities are provided.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1006.2 Means of Egress, Egress From Spaces
Two exits or exit access doorways from any space shall be provided where the design ...
Building Code 2015 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress From Spaces
1006.2.2.2 Means of Egress, Refrigeration Machinery Rooms
Machinery rooms larger than 1,000 square feet (93 m 2 ) shall have not less than two exits or exit access doorways . Where two exit access ...
Building Code 2015 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress From Spaces > 1006.2.2 Egress Based on Use > 1006.2.2.2 Refrigeration Machinery Rooms
1006.2.2.5 Means of Egress, Vehicular Ramps
Vehicular ramps shall not be considered as an exit access ramp unless pedestrian facilities are provided ...
Building Code 2015 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress From Spaces > 1006.2.2 Egress Based on Use > 1006.2.2.5 Vehicular Ramps
1006.2.1.1 Means of Egress, Three or More Exits or Exit Access Doorways
Three exits or exit access doorways shall be provided from any space with an occupant load of 501 to 1,000. Four exits or exit access doorways ...
Building Code 2015 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress From Spaces > 1006.2.1 Egress Based on Occupant Load and Common Path of Egress Travel Distance > 1006.2.1.1 Three or More Exits or Exit Access Doorways
402.8.6.1 Special Detailed Requirements Based on Use and Occupancy, Exit Passageways
Where exit passageways provide a secondary means of egress from a tenant space, doorways to the exit passageway shall be protected by 1-hour ...
Building Code 2015 of Utah > 4 Special Detailed Requirements Based on Use and Occupancy > 402 Covered Mall and Open Mall Buildings > 402.8 Means of Egress > 402.8.6 Access to Exits > 402.8.6.1 Exit Passageways
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Contact Careers Terms Privacy
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US