1006.2.2 Egress Based on Use

Building Code 2015 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress From Spaces > 1006.2.2 Egress Based on Use
JUMP TO FULL CODE CHAPTER
The numbers of exits or access to exits shall be provided in the uses described in Sections 1006.2.2.1 through 1006.2.2.5.

1006.2.2.1 Boiler, Incinerator and Furnace Rooms

Two exit access doorways are required in boiler, incinerator and furnace rooms where the area is over 500 square feet (46 m2) and any fuel-fired equipment exceeds 400,000 British thermal units (Btu) (422 000 KJ) input capacity. Where two exit access doorways are required, one is permitted to be a fixed ladder or an alternating tread device. Exit access doorways shall be separated by a horizontal distance equal to one-half the length of the maximum overall diagonal dimension of the room.

1006.2.2.2 Refrigeration Machinery Rooms

Machinery rooms larger than 1,000 square feet (93 m2) shall have not less than two exits or exit access doorways. Where two exit access doorways are required, one such doorway is permitted to be served by a fixed ladder or an alternating tread device. Exit access doorways shall be separated by a horizontal distance equal to one-half the maximum horizontal dimension of the room.

All portions of machinery rooms shall be within 150 feet (45 720 mm) of an exit or exit access doorway. An increase in exit access travel distance is permitted in accordance with Section 1017.1.

Doors shall swing in the direction of egress travel, regardless of the occupant load served. Doors shall be tight fitting and self-closing.

1006.2.2.3 Refrigerated Rooms or Spaces

Rooms or spaces having a floor area larger than 1,000 square feet (93 m2), containing a refrigerant evaporator and maintained at a temperature below 68°F (20°C), shall have access to not less than two exits or exit access doorways.

Exit access travel distance shall be determined as specified in Section 1017.1, but all portions of a refrigerated room or space shall be within 150 feet (45 720 mm) of an exit or exit access doorway where such rooms are not protected by an approved automatic sprinkler system. Egress is allowed through adjoining refrigerated rooms or spaces.

Exception: Where using refrigerants in quantities limited to the amounts based on the volume set forth in the International Mechanical Code.

1006.2.2.4 Day Care Means of Egress

Day care facilities, rooms or spaces where care is provided for more than 10 children that are 21/2 years of age or less, shall have access to not less than two exits or exit access doorways.

1006.2.2.5 Vehicular Ramps

Vehicular ramps shall not be considered as an exit access ramp unless pedestrian facilities are provided.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1006.2.2 Means of Egress, Egress Based on Use
The numbers of exits or access to exits shall be provided in the uses described in Sections 1006.2.2.1 through 1006.2.2.5 ...
Building Code 2015 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress From Spaces > 1006.2.2 Egress Based on Use
1006.2.2 Means of Egress, Egress based on use
Egress is allowed through adjoining refrigerated rooms or spaces. Exception: Where using refrigerants in quantities limited to the amounts based ...
Building Code 2018 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress from spaces > 1006.2.2 Egress based on use
1006.2.2.2 Means of Egress, Refrigeration machinery rooms
Machinery rooms larger than 1,000 square feet (93 m 2 ) shall have not less than two exits or exit access doorways . Where two exit access ...
Building Code 2018 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress from spaces > 1006.2.2 Egress based on use > 1006.2.2.2 Refrigeration machinery rooms
1006.2.2.4 Means of Egress, Day Care Means of Egress
to not less than two exits or exit access doorways ...
Building Code 2015 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress From Spaces > 1006.2.2 Egress Based on Use > 1006.2.2.4 Day Care Means of Egress
1006.2.2.4 Means of Egress, Group I-4 means of egress
to not less than two exits or exit access doorways ...
Building Code 2018 of Utah > 10 Means of Egress > 1006 Number of Exits and Exit Access Doorways > 1006.2 Egress from spaces > 1006.2.2 Egress based on use > 1006.2.2.4 Group I-4 means of egress
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US