C403.2.4.7 Economizer Fault Detection and Diagnostics (FDD)
JUMP TO FULL CODE CHAPTER
Air-cooled unitary direct-expansion units listed in Tables C403.2.3(1) through C403.2.3(3) and variable refrigerant flow (VRF) units that are equipped with an economizer in accordance with Section C403.3 shall include a fault detection and diagnostics (FDD) system complying with the following:
The following temperature sensors shall be permanently installed to monitor system operation:
- 1.1. Outside air.
- 1.2. Supply air.
- 1.3. Return air.
- Temperature sensors shall have an accuracy of ±2°F (1.1°C) over the range of 40°F to 80°F (4°C to 26.7°C).
- Refrigerant pressure sensors, where used, shall have an accuracy of ±3 percent of full scale.
The unit controller shall be capable of providing system status by indicating the following:
- 4.1. Free cooling available.
- 4.2. Economizer enabled.
- 4.3. Compressor enabled.
- 4.4. Heating enabled.
- 4.5. Mixed air low limit cycle active.
- 4.6. The current value of each sensor.
- The unit controller shall be capable of manually initiating each operating mode so that the operation of compressors, economizers, fans and the heating system can be independently tested and verified.
- The unit shall be capable of reporting faults to a fault management application accessible by dayto-day operating or service personnel, or annunciated locally on zone thermostats.
The FDD system shall be capable of detecting the following faults:
- 7.1. Air temperature sensor failure/fault.
- 7.2. Not economizing when the unit should be economizing.
- 7.3. Economizing when the unit should not be economizing.
- 7.4. Damper not modulating.
- 7.5. Excess outdoor air.
Related Code Sections
C403.2.4.7 [CE] Commercial Energy Efficiency, Economizer Fault Detection and Diagnostics (FDD)
that are equipped with an economizer in accordance with Section C403.3 shall include a fault detection and diagnostics (FDD) system complying with the following ...
Energy Conservation Code 2015 of Massachusetts > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.2 Provisions Applicable to All Mechanical Systems (Mandatory) > C403.2.4 HVAC System Controls > C403.2.4.7 Economizer Fault Detection and Diagnostics (FDD)
C403.5.5 [CE] Commercial Energy Efficiency, Economizer Fault Detection and Diagnostics (Mandatory)
that are equipped with an economizer in accordance with Sections C403.5 through C403.5.4 shall include a fault detection and diagnostics system complying ...
Energy Conservation Code 2018 of Massachusetts > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.5 Economizers (Prescriptive) > C403.5.5 Economizer Fault Detection and Diagnostics (Mandatory)
503.3.1 Commercial Energy Efficiency, Economizers
Supply air economizers shall be provided on each cooling system as shown in Table 503.3.1(1). Economizers shall be capable of providing 100-percent ...
Energy Conservation Code 2009 of Massachusetts > 5 Commercial Energy Efficiency > 503 Building Mechanical Systems > 503.3 Simple HVAC Systems and Equipment (Prescriptive) > 503.3.1 Economizers
C408.2.3.3 [CE] Commercial Energy Efficiency, Economizers
Air economizers shall undergo a functional test to determine that they operate in accordance with manufacturer's specifications ...
Energy Conservation Code 2018 of Massachusetts > 4 [CE] Commercial Energy Efficiency > C408 Maintenance Information and System Commissioning > C408.2 Mechanical Systems and Service Water-Heating Systems Commissioning and Completion Requirements > C408.2.3 Functional Performance Testing > C408.2.3.3 Economizers
C408.2.3.3 [CE] Commercial Energy Efficiency, Economizers
Air economizers shall undergo a functional test to determine that they operate in accordance with manufacturer's specifications ...
Energy Conservation Code 2015 of Massachusetts > 4 [CE] Commercial Energy Efficiency > C408 System Commissioning > C408.2 Mechanical Systems and Service Water-Heating Systems Commissioning and Completion Requirements > C408.2.3 Functional Performance Testing > C408.2.3.3 Economizers