At least four times the maximum intended load, except that each extra-heavy-duty type 1A metal or plastic ladder shall sustain at least 3.3 times the maximum intended load. The ability of a ladder to sustain the loads indicated in this paragraph shall be determined by applying or transmitting the requisite load to the ladder in a downward vertical direction. Ladders built and tested in conformance with the applicable provisions of appendix A of this subpart will be deemed to meet this requirement.

Related Code Sections

1926.1053(a)(1)(i) Stairways and Ladders, Each Self-Supporting Portable Ladder
At least four times the maximum intended load, except that each extra-heavy-duty type 1A metal or plastic ladder shall sustain at least 3.3 times ...
1926.1053(b)(10) Stairways and Ladders,
The top of a non-self-supporting ladder shall be placed with the two rails supported equally unless it is equipped with a single support attachment ...
1926.955 Electric Power Transmission and Distribution, Portable Ladders and Platforms
Requirements for portable ladders contained in Subpart X of this part apply in addition to the requirements of this section, except as specifically ...
1926.1053(b)(5)(i) Stairways and Ladders,
Non-self-supporting ladders shall be used at an angle such that the horizontal distance from the top support to the foot of the ladder ...
1926.955(b) Electric Power Transmission and Distribution, Special Ladders and Platforms
Portable ladders used on structures or conductors in conjunction with overhead line work need not meet § 1926.1053(b)(5)(i) and (b)(12). Portable ...