// CODE SNIPPET
R302.4 Dwelling Unit Rated Penetrations
JUMP TO FULL CODE CHAPTER
Penetrations of wall or floor-ceiling assemblies required to be fire-resistance rated in accordance with Section R302.2 or R302.3 shall be protected in accordance with this section.
Through penetrations of fire-resistance-rated wall or floor assemblies shall comply with Section R302.4.1.1 or R302.4.1.2.
Exception: Where the penetrating items are steel, ferrous or copper pipes, tubes or conduits, the annular space shall be protected as follows:
- In concrete or masonry wall or floor assemblies, concrete, grout or mortar shall be permitted where installed to the full thickness of the wall or floor assembly or the thickness required to maintain the fire-resistance rating, provided that both of the following are complied with:
- 1.1. The nominal diameter of the penetrating item is not more than 6 inches (152 mm).
- 1.2. The area of the opening through the wall does not exceed 144 square inches (92 900 mm2).
- The material used to fill the annular space shall prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E119 or UL 263 time temperature fire conditions under a positive pressure differential of not less than 0.01 inch of water (3 Pa) at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated.
Penetrations shall be installed as tested in the approved fire-resistance-rated assembly.
Penetrations shall be protected by an approved penetration firestop system installed as tested in accordance with ASTM E814 or UL 1479, with a positive pressure differential of not less than 0.01 inch of water (3 Pa) and shall have an F rating of not less than the required fire-resistance rating of the wall or floor-ceiling assembly penetrated.
Membrane penetrations shall comply with Section R302.4.1. Where walls are required to have a fire-resistance rating, recessed fixtures shall be installed so that the required fire-resistance rating will not be reduced.
Exceptions:
- Membrane penetrations of not more than 2-hour fire-resistance-rated walls and partitions by steel electrical boxes that do not exceed 16 square inches (0.0103 m2) in area provided that the aggregate area of the openings through the membrane does not exceed 100 square inches (0.0645 m2) in any 100 square feet (9.29 m2) of wall area. The annular space between the wall membrane and the box shall not exceed 1/8 inch (3.1 mm). Such boxes on opposite sides of the wall shall be separated by one of the following:
- 1.1. By a horizontal distance of not less than 24 inches (610 mm) where the wall or partition is constructed with individual noncommunicating stud cavities.
- 1.2. By a horizontal distance of not less than the depth of the wall cavity where the wall cavity is filled with cellulose loose-fill, rockwool or slag mineral wool insulation.
- 1.3. By solid fireblocking in accordance with Section R302.11.
- 1.4. By protecting both boxes with listed putty pads.
- 1.5. By other listed materials and methods.
- Membrane penetrations by listed electrical boxes of any materials provided that the boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing. The annular space between the wall membrane and the box shall not exceed 1/8 inch (3.1 mm) unless listed otherwise. Such boxes on opposite sides of the wall shall be separated by one of the following:
- 2.1. By the horizontal distance specified in the listing of the electrical boxes.
- 2.2. By solid fireblocking in accordance with Section R302.11.
- 2.3. By protecting both boxes with listed putty pads.
- 2.4. By other listed materials and methods.
- The annular space created by the penetration of a fire sprinkler provided that it is covered by a metal escutcheon plate.
- Ceiling membrane penetrations by listed luminaires or by luminaires protected with listed materials that have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing.
Related Code Sections
R302.4 Building Planning, Dwelling Unit Rated Penetrations
Penetrations of wall or floor-ceiling assemblies required to be fire-resistance rated in accordance with Section R302.2 or R302.3 shall be protected ...
Residential Code 2018 of Kansas > 3 Building Planning > R302 Fire-Resistant Construction > R302.4 Dwelling Unit Rated Penetrations
717.6.2 Fire and Smoke Protection Features, Membrane Penetrations
air duct penetrations protected in accordance with Section 714.5.2 are located within the cavity of a wall and do not pass through another dwelling unit ...
Building Code 2018 of Kansas > 7 Fire and Smoke Protection Features > 717 Ducts and Air Transfer Openings > 717.6 Horizontal Assemblies > 717.6.2 Membrane Penetrations
607.6.2 Duct Systems, Membrane Penetrations
of a wall and do not pass through another dwelling unit or tenant space. Where duct and air transfer openings are protected with a duct outlet ...
Mechanical Code 2018 of Kansas > 6 Duct Systems > 607 Duct and Transfer Openings > 607.6 Horizontal Assemblies > 607.6.2 Membrane Penetrations
607.6 Duct Systems, Horizontal Assemblies
through another dwelling unit or tenant space. Where duct and air transfer openings are protected with a duct outlet penetration system tested as part ...
Mechanical Code 2018 of Kansas > 6 Duct Systems > 607 Duct and Transfer Openings > 607.6 Horizontal Assemblies