605.4 Ductile Iron Pipe and Joints
JUMP TO FULL CODE CHAPTER
Ductile iron pipe and fitting joining methods shall be installed in accordance with the manufacturer's installation instructions and shall comply with Section 605.4.1 or Section 605.4.2.
Mechanical joints for ductile iron pipe and fittings shall consist of a bell that is cast integrally with the pipe or fitting and provided with an exterior flange having bolt holes and a socket with annular recesses for the sealing gasket and the plain end of the pipe or fitting. The elastomeric gasket shall comply with AWWA C111. Lubricant recommended for potable water application by the pipe manufacturer shall be applied to the gasket and plain end of the pipe.
Push-on joints for ductile iron pipe and fittings shall consist of a single elastomeric gasket that shall be assembled by positioning the elastomeric gasket in an annular recess in the pipe or fitting socket and forcing the plain end of the pipe or fitting into the socket. The plain end shall compress the elastomeric gasket to form a positive seal and shall be designed so that the elastomeric gasket shall be locked in place against displacement. The elastomeric gasket shall comply with AWWA C111. Lubricant recommended for potable water application by the pipe manufacturer shall be applied to the gasket and plain end of the pipe.
Related Code Sections
605.4 Water Supply and Distribution, Ductile Iron Pipe and Joints
joints for ductile iron pipe and fittings shall consist of a bell that is cast integrally with the pipe or fitting and provided with an exterior flange ...
Uniform Plumbing Code 2018 of Nevada > 6 Water Supply and Distribution > 605.0 Joints and Connections > 605.4 Ductile Iron Pipe and Joints
1211.7 Hydronics, Ductile Iron Pipe
Joints between ductile iron pipe or fittings shall be installed in accordance with one of the following methods:
Mechanical joints for ductile ...
Uniform Mechanical Code 2018 of Nevada > 12 Hydronics > 1211.0 Joints and Connections > 1211.7 Ductile Iron Pipe
10.1.1.1 Underground Requirements, Listing
and Fittings for Water
AWWA C104
Polyethylene Encasement for Ductile Iron Pipe Systems
AWWA C105
Rubber-Gasket Joints for Ductile Iron ...
Standard for the Installation of Sprinkler Systems 2016 of Nevada > 10 Underground Requirements > 10.1* Piping > 10.1.1* > 10.1.1.1 Listing
8.15.21 Installation Requirements, Dry Pipe Underground
Unprotected cast-iron or ductile-iron pipe shall be permitted where joined ...
Standard for the Installation of Sprinkler Systems 2016 of Nevada > 8 Installation Requirements > 8.15 Special Situations > 8.15.21 Dry Pipe Underground
G2414.10.4 Fuel Gas, (403.10.4) Metallic Fittings
, ductile iron or cast iron. Fittings used with copper or brass pipe shall be copper, brass or bronze. Cast-iron bushings shall be prohibited ...
Residential Code 2012 of Nevada > 24 Fuel Gas > G2414 (403) Piping Materials > G2414.10 (403.10) Metallic Piping Joints and Fittings > G2414.10.4 (403.10.4) Metallic Fittings