506.3.2.3 Duct-To-Exhaust Fan Connections
JUMP TO FULL CODE CHAPTER
Duct-to exhaust fan connections shall be flanged and gasketed at the base of the fan for vertical discharge fans; shall be flanged, gasketed and bolted to the inlet of the fan for side-inlet utility fans; and shall be flanged, gasketed and bolted to the inlet and outlet of the fan for in-line fans. Gasket and sealing materials shall be rated for continuous duty at a temperature of not less than 1500°F (816°C).
Related Code Sections
506.3.2.3 Exhaust Systems, Duct-To-Exhaust Fan Connections
Duct-to exhaust fan connections shall be flanged and gasketed at the base of the fan for vertical discharge fans; shall be flanged, gasketed ...
Mechanical Code of the Texas Industrialized Housing and Buildings Program > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.2 Joints, Seams and Penetrations of Grease Ducts > 506.3.2.3 Duct-To-Exhaust Fan Connections
504.9 Exhaust Systems, Commercial Clothes Dryers
materials. Clothes dryer transition ducts used to connect the appliance to the exhaust duct system shall be limited to single lengths not to exceed 8 ...
Mechanical Code of the Texas Industrialized Housing and Buildings Program > 5 Exhaust Systems > 504 Clothes Dryer Exhaust > 504.9 Commercial Clothes Dryers
506.5.1.1 Exhaust Systems, Fan Motor
Exhaust fan motors shall be located outside of the exhaust airstream ...
Mechanical Code of the Texas Industrialized Housing and Buildings Program > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.5 Exhaust Equipment > 506.5.1 Exhaust Fans > 506.5.1.1 Fan Motor
506.3.2.2 Exhaust Systems, Duct-To-Hood Joints
for inspection, and without grease traps.
Exceptions: This section shall not apply to:
A vertical duct-to-hood collar connection made ...
Mechanical Code of the Texas Industrialized Housing and Buildings Program > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.2 Joints, Seams and Penetrations of Grease Ducts > 506.3.2.2 Duct-To-Hood Joints
505.3 Exhaust Systems, Common Exhaust Systems for Domestic Kitchens Located in Multistory Structures
of the airstream.
The exhaust fan shall run continuously, and shall be connected to a standby power source.
Exhaust fan operation shall be monitored ...
Mechanical Code of the Texas Industrialized Housing and Buildings Program > 5 Exhaust Systems > 505 Domestic Kitchen Exhaust Equipment > 505.3 Common Exhaust Systems for Domestic Kitchens Located in Multistory Structures