Ductwork shall be tested to the maximum permitted leakage in 1 cubic foot per minute (ft3/min) per 100 square feet [0.0001 (m3/s)/m2] of duct surface area in accordance with SMACNA HVAC Air Duct Leakage Test Manual. Register penetrations shall be sealed during the test. The test shall be conducted with a pressure differential of 0.1 inch water gauge (0.02 kPa) across the tested system.

Related Code Sections

603.10.1 Duct Systems, Duct Leakage Tests
Ductwork shall be leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual. Representative sections totaling not less than 10 ...
510.5.3.1 Exhaust Systems, Duct Leakage Test
Prior to the use of or concealment of a portion of a grease duct system, a leakage test shall be performed to determine that all welded joints ...