// CODE SNIPPET
506.10 Duct Clearances
Go To Full Code Chapter
Unless the conditions in Section 506.10.1 or Section 506.10.2 exist, duct systems and system components shall have a clearance of at least 6 inches (152 mm) from stored combustible materials, and not less than 1/2 of an inch (13 mm) clearance from combustible construction. [NFPA 91:4.7.1]
506.10.1 Protection Provided
Where stored combustible material or combustible construction is protected from ductwork by the use of materials or products listed for protection purposes, clearance shall be maintained in accordance with those listings. [NFPA 91:4.7.1.1]
506.10.2 Systems Conveying Combustible Materials
Unless the conditions in Section 506.10.3 exist, duct systems and system components handling combustible material shall have a clearance of not less than 18 inches (457 mm) from combustible construction or a combustible material. [NFPA 91:4.7.2]
506.10.3 Reduced Clearance Permitted
When the ductwork system is operating at 140°F (60°C) or below and is equipped with an approved automatic extinguishing system designed for the specific hazard, the clearance shall be permitted to be reduced to 6 inches (152 mm) from combustible materials and 1/2 of an inch (12.7 mm) from combustible construction. [NFPA 91:4.7.2.1]
506.10.4 Clearance Increases
All duct systems and system components operating at temperatures above 140°F (60°C) shall have clearances from stored combustible materials or combustible construction not less than those listed in Table 506.10.4. [NFPA 91:4.7.3]
DUCT GAS TEMPERATURE | LARGEST DUCT DIMENSION (inches) | CLEARANCE (inches) |
---|---|---|
140°F — 600°F incl. | 8 | 8 |
>8 | 12 | |
>600°F — 900°F incl. | 8 | 18 |
>8 | 24 | |
>900°F | All ducts lined with refractory | 24 |
For SI units: 1 inch = 25.4 mm, °C=(°F—32)/1.8
506.10.4.1 Temperatures Over 900°F
Ducts handling materials at temperatures in excess of 900°F (482°C) shall be lined with refractory material or the equivalent. [NFPA 91:4.7.3.1]
506.10.4.2 Clearance Reduction
When stored combustible materials or combustible construction are protected from ductwork in accordance with Section 506.11, the clearance established in Table 506.10.4 shall be permitted to be reduced in accordance with Table 506.11, but not to less than specified in Section 506.10. [NFPA 91:4.7.3.2]
Upcodes Diagrams
Related Code Sections
506.10 Exhaust Systems, Duct Clearances
Unless the conditions in Section 506.10.1 or Section 506.10.2 exist, duct systems and system components shall have a clearance of at least 6 inches ...
931.5.5 Installation of Specific Appliances, Hood and Duct Clearances
A hood and duct serving a fuel-burning kiln shall have a clearance from combustible construction of not less than 18 inches (457 mm). This clearance ...
506.11.4 Exhaust Systems, Duct and Thermal Shield
With all clearance reduction systems, not less than 1 inch (25.4 mm) clear space shall be provided between the duct and the thermal shield. [NFPA 91 ...
506.11.6 Exhaust Systems, Reduce Clearance With Air Gaps
When using clearance reduction systems that include an air gap between the combustible surface and the selected means of protection, air circulation ...
506.10.4.1 Exhaust Systems, Temperatures Over 900°F
Ducts handling materials at temperatures in excess of 900°F (482°C) shall be lined with refractory material or the equivalent. [NFPA 91:4.7.3.1] ...