1310.2.2 Drops to Individual Stations
JUMP TO FULL CODE CHAPTER
Drops to individual station outlets and inlets shall be not less than DN15 (NPS 1/2) (5/8 inch O.D.) size. [NFPA 99:5.1.10.11.1.4]
For SI units: 1 pound-force per square inch = 6.8947 kPa, 1 inch of mercury = 3.386 kPa
TYPE OF SYSTEM | MAXIMUM ALLOWABLE SYSTEM PRESSURE LOSS (psi) |
---|---|
Medical Air | 5 |
Nitrogen | 15 |
Nitrous Oxide | 5 |
Carbon Dioxide | 5 |
Oxygen | 5 |
Medical Vacuum | 4 inches of mercury |
For SI units: 1 pound-force per square inch = 6.8947 kPa, 1 inch of mercury = 3.386 kPa
Related Code Sections
1310.2.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Drops to Individual Stations
Drops to individual station outlets and inlets shall be not less than DN15 (NPS 1 / 2 ) ( 5 / 8 inch O.D.) size. [NFPA 99:5.1.10.11.1.4 ...
California Plumbing Code 2019 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1310.0 Installation of Piping > 1310.2 Required Pipe Sizing > 1310.2.2 Drops to Individual Stations
1310.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Required Pipe Sizing
) size. [NFPA 99:5.1.10.11.1.3]
Drops to individual station outlets and inlets shall
be not less than DN15 (NPS 1 / 2 ) ( 5 / 8 of an inch
O.D.) size ...
California Plumbing Code 2016 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1310.0 Installation of Piping > 1310.2 Required Pipe Sizing
806.1.3 Interior Finish, Decorative Materials and Furnishings, Dryness
, Division 1, ยง3.08]. Decorative Materials. In every Group A, E, I, R-1, R-2, R-2.1, R-3.1 and R-4 occupancy, all drapes, hangings, curtains, drops ...
California Fire Code 2019 > 8 Interior Finish, Decorative Materials and Furnishings > 806 Natural Decorative Vegetation in New and Existing Buildings > 806.1 Natural Cut Trees > 806.1.3 Dryness
1319.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Certification Tests
of pipelines, station outlets, and control valves.
Testing for cross-connection, flow rate, system pressure drop, and system performance ...
California Plumbing Code 2019 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1319.0 System Certification > 1319.2 Certification Tests
1320.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Certification Tests
of pipelines,
station outlets, and control valves.
Testing for cross-connection, flow rate, system pressure drop, and system performance ...
California Plumbing Code 2016 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1320.0 System Certification > 1320.2 Certification Tests