Section P2909 Drinking Water Treatment Units
JUMP TO FULL CODE CHAPTER
Drinking water treatment units shall meet the requirements of NSF42, NSF 44, NSF 53, NSF 60 or CSA B483.1.
Point-of-use reverse osmosis drinking water treatment units, designed for residential use, shall meet the requirements of CSA B483.1 or NSF 58. Waste or discharge from reverse osmosis drinking water treatment units shall enter the drainage system through an air gap or an air gap device that meets the requirements of NSF 58.
The tubing to and from drinking water treatment units shall be of a size and material as recommended by the manufacturer. The tubing shall comply with NSF 14, NSF 42, NSF 44, NSF 53, NSF 58 or NSF 61.
Related Code Sections
Section 611 Water Supply and Distribution, Drinking Water Treatment Units
Point-of-use reverse osmosis drinking water treatement units shall comply with NSF 58 or CSA B483.1. Drinking water treatment units shall meet ...
Section P2909 Water Supply and Distribution, Drinking Water Treatment Units
Drinking water treatment units shall meet the requirements of NSF42, NSF 44, NSF 53, NSF 60 or CSA B483.1 ...
Residential Code 2018 of Kansas > 29 Water Supply and Distribution > P2909 Drinking Water Treatment Units
P2909.3 Water Supply and Distribution, Connection Tubing
The tubing to and from drinking water treatment units shall be of a size and material as recommended by the manufacturer. The tubing shall comply ...
Residential Code 2018 of Kansas > 29 Water Supply and Distribution > P2909 Drinking Water Treatment Units > P2909.3 Connection Tubing
Chapter 15 Referenced Standards
of Grease Interceptors
1003.3.5
B483.1—07(R2012)
Drinking Water Treatment Units
611.1, 611.2
B602—15
Mechanical Couplings ...
Section 410 Fixtures, Faucets and Fixture Fittings, Drinking Fountains
Drinking fountains shall conform to ASME A112.19.1/CSA B45.2 or ASME A112.19.2/CSA B45.1 and water coolers shall conform to ASHRAE 18. Drinking ...