Where a water heater is located in an attic, in or on an attic ceiling assembly, floor-ceiling assembly, or floor-subfloor assembly where damage results from a leaking water heater, a watertight pan of corrosion-resistant materials shall be installed beneath the water heater with not less than 3/4 of an inch (20 mm) diameter drain to an approved location. Such pan shall be not less than 11/2 inches (38 mm) in depth.
Upcodes Diagrams

Related Code Sections

507.5 Water Heaters, Drainage Pan
results from a leaking water heater, a watertight pan of corrosion-resistant materials shall be installed beneath the water heater with not less than 3/4 ...
M1411.5 Heating and Cooling Equipment and Appliances, Auxiliary Drain Pan
in the condensate drainage system. These pans shall be installed in accordance with the applicable provisions of Section M1411.3. Exception: Fuel-fired ...
G2404.10 Fuel Gas, (307.5) Auxiliary Drain Pan
of stoppage in the condensate drainage system. Such pan shall be installed in accordance with the applicable provisions of Section M1411. Exception: An ...
10.2.3 Construction and System Start-Up, Testing of Drain Pans
To minimize conditions of water stagnation that may result in microbial growth, inspect drain pans to verify proper drainage under operating ...
R703.4 Wall Covering, Flashing
as to direct water to the surface of the exterior wall finish or to the water-resistive barrier for subsequent drainage. Openings using pan flashing shall ...