Type of Fixture
D.F.U./Fixture (Load)
Minimum Size of Trap(inches)
Bathroom groups:
1 tank water closet, 1 lavatory with 11/4 inch trap and 1 bathtub1 or shower stall
7
11/4
1 water closet with flush valve, 1 lavatory with 11/4 inch trap and 1 bathtub or shower1
11
 
Bathtub (with or without overhead shower)1
2
11/2
Bathtub1
3
2
Bidet
2
11/2
Clothes washer, automatic
3
2
Dental unit or cuspidor
1
11/4
Drinking fountain
1/2
1
Dishwasher2, domestic
2
11/2
Floor drains
See Appendix A, Table F
2
Lavatories:
 
 
Lavatory
1
11/4
Lavatory
2
11/2
Lavatory, barber, beauty parlor
2
11/2
Lavatory, dental
1
11/4
Lavatory, surgeon's
2
11/2
Laundry tray (1 or 2 compartments)
2
11/2


Type of Fixture
D.F.U./Fixture (Load)
Minimum Size of Trap(inches)
Shower stall
3
2
Showers (group) per head2
3
2

Sinks:
   
Combination sink and tray
3
11/2
Combination sink and tray with
food-disposal unit
4 Separate Traps
11/2
Flushing rim (with valve)
8
3
Kitchen sink, domestic
2
11/2
Kitchen sink, domestic, with food-waste grinder
3 Separate Traps
11/2
Pot, scullery, etc.2
4
11/2
Service (P trap)
3
3
Service (P trap)
2
2
Surgeon's
3
11/2
Wash sink(circular or multiple),
each set of faucets
2


11/2
Urinals:
 
 
Urinal, pedestal, siphon jet, blowout
8
2
Urinal stall
3
2
Urinal, wall integral trap
3
2
Urinal, wall P trap, exposed
2
11/2
Water closets:
 
 
Tank operated
4
3
Valve-operated
8
3

  1. 1A shower head over a bathtub does not increase the fixture value.
  2. 2See Appendix A:  Table F and Section 890.1330(b) for method of determining unit values of fixtures not listed in this Table or for rating of devices with intermittent flows.
(Source: Amended at 28 Ill. Reg. 4215, effective February 18, 2004)

Related Code Sections

Section 890.1330 Drainage System, Drainage Fixture Units (DFUs)
Values for Fixtures. Drainage fixture units (DFUs) (see Appendix A.Table E) designate the relative load of different kinds of fixtures that shall ...
2902.1 Plumbing Systems, Minimum Number of Fixtures
, motels, boarding houses (transient) 1 per sleeping unit 1 per sleeping unit 1 per sleeping unit — 1 service sink Dormitories ...
2902.1 Plumbing Systems, Minimum Number of Fixtures
, boarding houses (transient) 1 per sleeping unit 1 per sleeping unit 1 per sleeping unit — 1 service sink Dormitories, fraternities ...