312.2.2 Drainage and Vent Rough-in Air Test
Go To Full Code Chapter
When permitted by the manufacturer of the piping, fittings, and solvent cement (if part of the plumbing system), an air test shall be made by forcing air into the system until there is a uniform gauge pressure of 5 psi (34.5 kPa) or sufficient to balance a 10-inch (254 mm) column of mercury. This pressure shall be held for a test period of at least 15 minutes. Any adjustments to the test pressure required because of changes in ambient temperature or the seating of gaskets shall be made prior to the beginning of the testperiod. Testing shall be done with a dual pressure relief valve rated for 7.5 psig.
Related Code Sections
312.2.2 General Regulations, Drainage and Vent Rough-in Air Test
When permitted by the manufacturer of the piping, fittings, and solvent cement (if part of the plumbing system), an air test shall be made by forcing ...
312.2.2 General Regulations, Drainage and Vent Rough-in Air Test
When permitted
by the manufacturer of the piping, fittings, and solvent
cement (if part of the plumbing system), an air test
shall be made by forcing ...
312.2 General Regulations, Drainage and Vent Rough-in Test
), an
alternative method of testing the drainage and vent system,
such as compressed gas or vacuum, may be permitted
to meet the drainage and vent rough ...
312.2.1 General Regulations, Drainage and Vent Rough-in Water Test
A water
test shall be applied to the drainage system either in its
entirety or in sections. If applied to the entire system, all
openings ...
312.2.3 General Regulations, Alternative Drainage and Vent Rough-in Test
the drainage and vent system,
such as compressed gas or vacuum, may be permitted
to meet the drainage and vent rough-in test requirements
of this code ...