2311.2.3 Drainage and Disposal of Liquids and Oil-Soaked Waste
JUMP TO FULL CODE CHAPTER
Garage floor drains, where provided, shall drain to approved oil separators or traps discharging to a sewer in accordance with the International Plumbing Code. Contents of oil separators, traps and floor drainage systems shall be collected at sufficiently frequent intervals and removed from the premises to prevent oil from being carried into the sewers.
Crankcase drainings and liquids shall not be dumped into sewers, streams or on the ground, but shall be stored in approved tanks or containers in accordance with Chapter 57 until removed from the premises.
Self-closing metal cans shall be used for oily waste.
Related Code Sections
2311.2.3 Motor Fuel-Dispensing Facilities and Repair Garages, Drainage and Disposal of Liquids and Oil-Soaked Waste
Plumbing Code . Contents of oil separators, traps and floor drainage systems shall be collected at sufficiently frequent intervals and removed from ...
2020 Minnesota State Fire Code > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2311 Repair Garages > 2311.2 Storage and Use of Flammable and Combustible Liquids > 2311.2.3 Drainage and Disposal of Liquids and Oil-Soaked Waste
2311.2.3 Motor Fuel-Dispensing Facilities and Repair Garages, Drainage and Disposal of Liquids and Oil-Soaked Waste
Plumbing Code . Contents of oil separators, traps and floor drainage systems shall be collected at sufficiently frequent intervals and removed from ...
Minnesota Fire Code 2015 > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2311 Repair Garages > 2311.2 Storage and Use of Flammable and Combustible Liquids > 2311.2.3 Drainage and Disposal of Liquids and Oil-Soaked Waste
5706.3.2 Flammable and Combustible Liquids, Waste Control
oil, waste oil, refuse or waste material ...
2020 Minnesota State Fire Code > 57 Flammable and Combustible Liquids > 5706 Special Operations > 5706.3 Well Drilling and Operating > 5706.3.2 Waste Control
5706.3.2 Flammable and Combustible Liquids, Waste Control
oil, waste oil, refuse or waste material ...
Minnesota Fire Code 2015 > 57 Flammable and Combustible Liquids > 5706 Special Operations > 5706.3 Well Drilling and Operating > 5706.3.2 Waste Control
2311.2.2 Motor Fuel-Dispensing Facilities and Repair Garages, Waste Oil, Motor Oil and Other Class IIIB Liquids
Waste oil, motor oil and other Class IIIB liquids shall be stored in approved tanks or containers, which are allowed to be stored and dispensed ...
2020 Minnesota State Fire Code > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2311 Repair Garages > 2311.2 Storage and Use of Flammable and Combustible Liquids > 2311.2.2 Waste Oil, Motor Oil and Other Class IIIB Liquids